Installer Parameters Via Networker; Networker Installer Parameter Kun4 & Kun5 - Kaden KEX Series Installer Manual

Ducted gas heaters
Table of Contents

Advertisement

9.2

INSTALLER PARAMETERS VIA NETWORKER

9.2.1 Networker Installer Parameter KUN4 & KUN5
No.
Display
1
H01 ID01: 1350
2
H01 ID02: 1350
3
H01 ID03: 950
4
H01 ID04: 1
5
H01 ID05: 500
6
H01 ID06: 65
7
H01 ID07: 0
8
H01 ID08: 1000
9
H01 ID09: 0
10
H01 ID10: 30
HEATING: MAXIMUM FAN SPEED SETTING
The number displayed is the default fan speed setting. That is, the fan RPM setting for normal
heating operation. This setting can be adjusted from 500 to 1450 and should be set to meet
the installation airflow requirements. It is recommended that a fan speed of at least 1000 be
selected as lower speeds are more likely to result in overheating if the system has not been
balanced correctly.
COOLING: MAXIMUM FAN SPEED SETTING
The fan RPM setting for normal cooling operation. This setting can be adjusted from 500 to
1350.
HEATING: ZONING MINIMUM FAN SPEED SETTING
The minimum RPM to which the fan will operate with the maximum number of outlets closed,
with the networker zoning in heating mode. This setting can be adjusted from 500 to 1350
(default is 950).
HEATER IDENTIFICATION NUMBER
(Do not alter unless multiple heaters are installed)
In systems with multiple heaters installed, identifies each heater unit in priority order, for
example ID04: 1, ID04: 2, ID04: 3.
CIRCULATION FAN OPERATION
The fan RPM setting in circulation mode. That is, fan operation between heating or cooling
cycles when the set room temperature has been achieved.
SUPPLY AIR THERMISTOR SET POINT TEMPERATURE
The temperature that the heater gas valve modulates to maintain. This setting can be
adjusted from 45°C to 70°C (default setting varies between different models) and should be
set to provide a comfortable outlet temperature.
ZONE/REFRIGERATION /HUMIDIFIER MODE
Value
System
Configuration
Heating
0
1
Heating
Heating + Add-On
2
Heating +
3
Humidification
Heating +
Humidification +
4
Add-On
5
Heating
Heating +
6
Add-On
Heating +
7
Add-On
COOLING: ZONING MINIMUM FAN SPEED SETTING
The minimum RPM to which the fan will operate with the maximum number of outlets closed,
with the networker zoning in heating mode.
DO NOT SET BELOW 1000
DO NOT ADJUST
Damper motor Open/Close time can be adjusted between 5 and 240 seconds - factory default
30 seconds
Table 7
Description
Zone
Connection
Connection
N/A
Heater PCB – up to 4
Heater PCB – up to 4
Heater PCB
'ADD-ON' terminal
Heater PCB – up to 4
Heater PCB – up to 3
Heater PCB
(A,B,C)
'ADD-ON' terminal
Zone Module – 1 only
(D)
Zone Module – up to 4
Zone Module – up to 4
Heater PCB
'ADD-ON' terminal
Zone Module – up to 3
Zone Module
'ADD-ON' terminal
Add-On
Humidifier
Connection
N/A
N/A
N/A
N/A
N/A
N/A
Heater PCB 'ADD-
ON' terminal
N/A
N/A
N/A
N/A
N/A