Offgridtec IC-24/3000/100/80 User Manual page 44

Inverter/charger
Table of Contents

Advertisement

F.
Boost Reconnect Charging voltage > Low Voltage Disconnect Voltage
2)
In the 48V input voltage system, the following rules must be followed when modifying the parameter
values in the user battery type for a Lead-acid battery.
A.
Over Voltage Disconnect Voltage ≥ Over Voltage Reconnect Voltage+1V
Over Voltage Disconnect Voltage > Charging Limit Voltage ≥ Equalize Charging Voltage ≥ Boost Charging
B.
Voltage ≥ Float Charging Voltage > Boost Reconnect Charging Voltage
C.
Low Voltage Reconnect Voltage ≥ Low Voltage Disconnect Voltage+1V
D.
Low Voltage Reconnect Voltage > Low Voltage Disconnect Voltage ≥ Discharging Limit Voltage (42.4V)
Under Voltage Warning Reconnect Voltage-1V ≥ Under Voltage Warning Voltage ≥ Discharging Limit Voltage
E.
(42.4V)
F.
Boost Reconnect Charging voltage > Low Voltage Disconnect Voltage
3)
In the 24V input voltage system, the following rules must be followed when modifying the parameter
values in the user battery type for a lithium battery.
A.
Over Voltage Disconnect Voltage ≥ Over Voltage Reconnect Voltage+0.5V
Over Voltage Disconnect Voltage > Over Voltage Reconnect Voltage=Charging Limit Voltage ≥ Equalize
B.
Charging Voltage=Boost Charging Voltage ≥ Float Charging Voltage > Boost Reconnect Charging Voltage
Low Voltage Reconnect Voltage ≥ Low Voltage Disconnect Voltage+0.5V
C.
D.
Low Voltage Reconnect Voltage > Low Voltage Disconnect Voltage ≥ Discharging Limit Voltage (21.2V)
E.
Under Voltage Warning Reconnect Voltage-0.5V ≥ Under Voltage Warning Voltage ≥ Discharging Limit
Voltage (21.2V)
F.
Boost Reconnect Charging Voltage> Low Voltage Reconnect Voltage
4)
In the 48V input voltage system, the following rules must be followed when modifying the parameter
values in the user battery type for a lithium battery.
A.
Over Voltage Disconnect Voltage ≥ Over Voltage Reconnect Voltage+1V
Over Voltage Disconnect Voltage > Over Voltage Reconnect Voltage=Charging Limit Voltage ≥ Equalize
B.
Charging Voltage=Boost Charging Voltage ≥ Float Charging Voltage > Boost Reconnect Charging Voltage
Low Voltage Reconnect Voltage ≥ Low Voltage Disconnect Voltage+1V
C.
D.
Low Voltage Reconnect Voltage>Low Voltage Disconnect Voltage ≥ Discharging Limit Voltage(42.4V)
E.
Under Voltage Warning Reconnect Voltage-1V ≥ Under Voltage Warning Voltage ≥ Discharging Limit Voltage
(42.4V)
F.
Boost Reconnect Charging Voltage > Low Voltage Reconnect Voltage
The lithium battery's voltage parameters must be set according to the voltage parameters of
BMS.
WARNING
42

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ic-48/5000/80/601-01-0137001-01-013705

Table of Contents