F.
Boost Reconnect Charging voltage > Low Voltage Disconnect Voltage
2)
In the 48V input voltage system, the following rules must be followed when modifying the parameter
values in the user battery type for a Lead-acid battery.
A.
Over Voltage Disconnect Voltage ≥ Over Voltage Reconnect Voltage+1V
Over Voltage Disconnect Voltage > Charging Limit Voltage ≥ Equalize Charging Voltage ≥ Boost Charging
B.
Voltage ≥ Float Charging Voltage > Boost Reconnect Charging Voltage
C.
Low Voltage Reconnect Voltage ≥ Low Voltage Disconnect Voltage+1V
D.
Low Voltage Reconnect Voltage > Low Voltage Disconnect Voltage ≥ Discharging Limit Voltage (42.4V)
Under Voltage Warning Reconnect Voltage-1V ≥ Under Voltage Warning Voltage ≥ Discharging Limit Voltage
E.
(42.4V)
F.
Boost Reconnect Charging voltage > Low Voltage Disconnect Voltage
3)
In the 24V input voltage system, the following rules must be followed when modifying the parameter
values in the user battery type for a lithium battery.
A.
Over Voltage Disconnect Voltage ≥ Over Voltage Reconnect Voltage+0.5V
Over Voltage Disconnect Voltage > Over Voltage Reconnect Voltage=Charging Limit Voltage ≥ Equalize
B.
Charging Voltage=Boost Charging Voltage ≥ Float Charging Voltage > Boost Reconnect Charging Voltage
Low Voltage Reconnect Voltage ≥ Low Voltage Disconnect Voltage+0.5V
C.
D.
Low Voltage Reconnect Voltage > Low Voltage Disconnect Voltage ≥ Discharging Limit Voltage (21.2V)
E.
Under Voltage Warning Reconnect Voltage-0.5V ≥ Under Voltage Warning Voltage ≥ Discharging Limit
Voltage (21.2V)
F.
Boost Reconnect Charging Voltage> Low Voltage Reconnect Voltage
4)
In the 48V input voltage system, the following rules must be followed when modifying the parameter
values in the user battery type for a lithium battery.
A.
Over Voltage Disconnect Voltage ≥ Over Voltage Reconnect Voltage+1V
Over Voltage Disconnect Voltage > Over Voltage Reconnect Voltage=Charging Limit Voltage ≥ Equalize
B.
Charging Voltage=Boost Charging Voltage ≥ Float Charging Voltage > Boost Reconnect Charging Voltage
Low Voltage Reconnect Voltage ≥ Low Voltage Disconnect Voltage+1V
C.
D.
Low Voltage Reconnect Voltage>Low Voltage Disconnect Voltage ≥ Discharging Limit Voltage(42.4V)
E.
Under Voltage Warning Reconnect Voltage-1V ≥ Under Voltage Warning Voltage ≥ Discharging Limit Voltage
(42.4V)
F.
Boost Reconnect Charging Voltage > Low Voltage Reconnect Voltage
The lithium battery's voltage parameters must be set according to the voltage parameters of
BMS.
WARNING
42