Toshiba RAV-SM302KRTP-UL Installation Manual page 49

Hide thumbs Also See for RAV-SM302KRTP-UL:
Table of Contents

Advertisement

Wired
Wireless remote controller
remote
Sensor block display of
controller
receiving unit
display
Operation Timer
Indication
Ready
Flashing
GR GR OR
F10
ALT
F12
ALT
F13
ALT
F15
ALT
F29
SIM
F31
SIM
H01
H02
H03
H04
H06
L03
SIM
L07
SIM
L08
SIM
L09
SIM
L10
SIM
L20
SIM
L29
SIM
L30
SIM
L31
SIM
Judging
Main defective parts
device
Indoor unit room temp.
Indoor
sensor (TA) error
TS sensor error
Outdoor
Heat sink sensor error
Outdoor
Temp. sensor connection
Outdoor
error
Indoor unit, other P.C.
Indoor
board error
Outdoor unit P.C. board
Outdoor
Outdoor unit compressor
Outdoor
breakdown
Outdoor unit compressor
Outdoor
lock
Outdoor unit current
Outdoor
detect circuit error
Case thermostat
Outdoor
operation
Outdoor unit
low-pressure system
Outdoor
error
Duplicated header
Indoor
indoor units
Group line in individual
Indoor
indoor unit
Indoor group address not
Indoor
set
Indoor unit capacity
Indoor
not set
Outdoor unit P.C. board
Outdoor
Network
adapter
LAN communication error
central
control
Other outdoor unit error
Outdoor
Abnormal external input
Indoor
into indoor unit (interlock)
Phase sequence error,
Outdoor
etc.
‒ 48 ‒
Parts to be checked / error description
Room temp. sensor (TA), indoor P.C.
board --- Open-circuit or short-circuit of the
room temp. sensor (TA) was detected.
TS sensor may be displaced,
disconnected or short-circuited.
Abnormal temperature was detected by
the temp. sensor of the IGBT heat sink.
Temp. sensor (TE / TS) may be connected
incorrectly.
Indoor P.C. board --- EEPROM error.
Outdoor P.C. board ---- In the case of
EEPROM error.
Current detect circuit, power voltage ---
Minimum frequency was reached in the
current releasing control or short-circuit
current (Idc) after direct excitation was
detected.
Compressor circuit --- Compressor lock
was detected.
Current detect circuit, outdoor unit P.C.
board --- Abnormal current was detected
in AC-CT or a phase loss was detected.
Malfunction of the case thermostat
Current, high-pressure switch circuit,
outdoor P.C. board --- Pressure sensor
error was detected or low-pressure
protective operation was activated.
Indoor address setting error --- There are
two or more header units in the group.
Indoor address setting error --- There is
at least one group-connected indoor unit
among individual indoor units.
Indoor address setting error --- Indoor
address group has not been set.
Indoor unit capacity has not been set.
In the case of outdoor P.C. board jumper
wire (for service) setting error.
Address setting, central control
remote controller, network adapter ---
Duplication of address in central control
communication.
Other outdoor unit error.
1) Communication error between IPDU
MCU and CDB MCU.
2) Abnormal temperature was detected by
the heat sink temp. sensor in IGBT.
External devices, outdoor unit P.C. board
--- Abnormal stop due to incorrect external
input into CN80.
Power supply phase sequence, outdoor
unit P.C. board --- Abnormal phase
sequence of the 3-phase power supply.
Installation Manual
Air conditioner
status
Auto-reset
Entire-stop
Entire stop
Entire stop
Auto-reset
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Auto-reset
Entire stop
EN
Entire stop
FR
Entire stop
ES
Operation
continued
(thermostat
OFF)
48-EN