Navien NFC-250/175H Installation Manual page 83

Condensing combi-boilers
Hide thumbs Also See for NFC-250/175H:
Table of Contents

Advertisement

When linking multiple water heaters to NFC-H combi-boiler, only the main unit can provide space heating and
sub units must be configured for DHW only (You can set only the NFC-H combi-boiler as the main unit in the
cascade system, and the main unit controls the power on/off status of all the sub units in the system).
Once turned on by the main unit, the water heaters will operate in stages to satisfy the DHW demands.
After completing the cascade settings and saving the changes, the boiler and water heater units must be
turned off then turned back on for the changes to take effect.
If errors occur while operating a cascade system, the relevant errors are displayed in the display of the failing
unit.
Power supply to the units must be OFF during the system piping.
The recommended recirculation flow rate for each water heater is 2-4 GPM. Depending on the
Note
number of water heaters and the diameter of the recirculation line, it may not be necessary to
connect all the NPE-A2 series water heaters to the recirculation line. If this is the case, set any
unconnected"A"model water heaters to Internal Recirculation Mode.
For any NPE-A2 water heater that is connected to the recirculation line, each individual unit must
be set to the proper recirculation mode utilizing the 2-way valve and front panel DIP switches. Refer
to the NPE Installation Manual for additional details.
8.1.1 Piping Sizes and Considerations
When plumbing a cascading system, consider the following pipe diameters and flow rates. Note that flow rates
above 6.6 ft/s may cause pipe erosion. These specifications may vary depending on installation conditions.
Piping Sizes for an NFC-H Boiler with up to 15 NPE-240A2 or NPE-240S2 Water Heaters
Model
NPE-240A2
NFC-H
or
NPE-240S2
1
2
3
4
5
6
7
1
8
9
10
11
12
13
14
15
ΔT=54°F Flow rate
Water Velocity
(GPM)
14.38
21.57
28.77
35.96
43.15
50.34
57.5
64.72
71.92
79.11
86.30
93.49
100.68
107.87
115.07
Pipe Diameter (mm/in)
(ft/s)
5.61
25A
5.54
30A
5.21
40A
6.53
40A
4.49
50A
5.24
50A
6.00
50A
4.39
65A
4.75
65A
5.34
65A
5.84
65A
6.33
65A
6.79
65A
5.11
80A
5.44
80A
1 in.
1
/
in.
1
4
1
/
in.
1
2
1
/
in.
1
2
2 in.
2 in.
2 in.
2
/
in.
1
2
2
/
in.
1
2
2
/
in.
1
2
2
/
in.
1
2
2
/
in.
1
2
2
/
in.
1
2
3 in.
3 in.
Installing a Cascade System
83