STEP 1 Before Installing
Read the Installation & Operation Manual before installing.
This product must be installed and serviced by a licensed plumber,
a licensed gas fitter, or a professional service technician. Navien is
not liable for any damages or defects resulting from improper
installation.
WARNING
Follow all local codes and/or the most recent edition of the National Fuel Gas Code (ANSI
Z223.1/NFPA 54) in the USA, or the Natural Gas and Propane Installation Code in Canada
(CAN/CGA B149.1).
Safety
DO NOT install the boiler in areas with excessively high humidity.
STEP 2 Installing
Unpacking
User's Information
Navien
Manual,
Condensing
Installation &
Boiler
Operation Manual
High Altitude
Air Vent
Conversion Kit
(Natural Gas Only)*
Tapping Screws
Pressure Relief
and Anchors
Valve, Heating
Air Vent
Outdoor
Bushing
Temperature
3
1
(
/
in to
/
in)
Sensor and Cable
4
2
Wall Mounting
Wall Flanges
Bracket
Spare Parts
* High Altitude Conversion kit and Propane Conversion kit are attached
to the inside of Product's cover.
Mounting on the Wall
CAUTION
Do not install the boiler on dry walls without proper reinforcement.
Drill in the supplied anchor bolts
1
after considering where the vent
termination will be located.
Secure the mounting bracket to the wall
2
with the tapping screws and anchors.
Quick Installation Guide
Quick
Installation
Manual
Propane
Conversion
Kit*
2 in Vent
Termination
Caps
Condensate
Trap
Universal
Temperature
Sensor
Lift up the boiler, rest the unit on the hooks
provided on the wall bracket on the wall.
Location Requirements
Select the best location on "Choosing an Installation Location" in the Installation &
Operation Manual.
Allowable minimum clearances
Top
Back
Side
Side
Front
Bottom
Checking the Rating Plate
>
WARNING
Before connecting the gas supply, determine the gas type and pressure for the boiler by
referring to the rating plate. Use only the same gas type indicated on the rating plate. Using a
different gas type will result in abnormal combustion and malfunction of the boiler. Gas
supplies should be connected by a licensed professional only.
The appliance and its gas connection must be leak tested before placing the appliance in
operation.
This boiler cannot be converted from natural gas to propane or vice versa without a Navien gas
conversion kit. Do not attempt a field conversion of this boiler without a Navien gas conversion
kit. Doing so will result in dangerous operating conditions and will void the warranty.
Navien Inc. is not liable for any property damage and/or personal injury resulting from
improper conversions.
Removing the Front Cover
>
Unclasp the 4 buckles that fix
the cover to the boiler, and then
remove the cover by lifting it
and pulling it outward.
1
Model
NFC-250/175H
NFC-250/200H
28884 049
Clearance
Indoor Installation
Top
9 in (229 mm) minimum
Back
0.5 in (13 mm) minimum
Front
4 in (100 mm) minimum
Sides
3 in (76 mm) minimum
Bottom
12 in (300 mm) minimum
This boiler is configured
for Natural Gas from the
factory. If conversion to
Propane Gas is required,
the Propane Conversion
Kit supplied with the boiler
must be used.
>
>

Advertisement

loading

Summary of Contents for Navien NFC-250/175H

  • Page 1 The appliance and its gas connection must be leak tested before placing the appliance in operation. High Altitude Propane This boiler cannot be converted from natural gas to propane or vice versa without a Navien gas Air Vent Conversion Kit Conversion conversion kit.
  • Page 2 Outlet (DHW) Inlet (DHW) You may install the pressure relief valve on the space heating supply of the Navien Manifold System, or on the top connection along with the air vent (and an external LWCO, if required). Auto Feeder Inlet...
  • Page 3 Combusion Air Intake Exhaust Gas Venting Length Exhaust Vent Piping Materials All Navien boilers are Category IV appliances. 3” pipe venting 2” pipe venting The venting system should be approved for use with Category IV appliances (typically Type BH Special Gas Vent approved by UL 1738-S636).
  • Page 4 STEP 3 After Installing Opening All the Valves > Gas Valve Space Heating System Valves Shut-off valves Navien, Inc. Closed Opened 20 Goodyear, Irvine, CA 92618 Tel: 1-800-519-8794, Fax: 1-949-420-0430 Gas Valve www.navieninc.com Operating the Boiler > Power ON Adjust Temperatures...

This manual is also suitable for: