Measuring The Inlet Gas Pressure - Navien NFC-250/175H Installation Manual

Condensing combi-boilers
Hide thumbs Also See for NFC-250/175H:
Table of Contents

Advertisement

Maximum Liquefied Propane Delivery Capacity
In Thousands of BTU/H (0.5 in WC pressure drop)
Length (including fittings)
Pipe
10 ft
20 ft
30 ft
Size
(3 m)
(6 m)
(9 m)
/
in
291
200
160
1
2
/
in
608
418
336
3
4
1 in
1,150 787
632
1
/
in 2,350 1,620 1,300 1,110 985
1
4
1
/
in 3,520 2,420 1,940 1,660 1,480 1,340 1,230 1,140 1,070 1,010 899
1
2
2 in
6,790 4,660 3,750 3,210 2,840 2,570 2,370 2,200 2,070 1,950 1,730 1,570

4.2 Measuring the Inlet Gas Pressure

WARNING
The boiler cannot function properly without sufficient inlet gas pressure. Measuring the inlet gas pressure
should be performed by a licensed professional only.
The inlet gas pressure must be maintained between 3.5 in and 10.5 in WC for natural gas and between 8.0 in
and 13.0 in WC for liquefied propane.
The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in excess of
The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff
valve during any pressure testing of the gas supply piping system at test pressures equal to or less than
(3.5 kPa).
If gas pressure is out of the acceptable range or an excessive pressure drop is observed, contact the
Note
gas supplier or a qualified installer to supply proper gas pressure to the unit.
60
Connecting the Gas Supply
40 ft
50 ft
60 ft
80 ft
(12 m)
(15 m)
(18 m)
(24 m)
137
122
110
101
287
255
231
212
541
480
434
400
892
821
100 ft
125 ft
150 ft
175 ft
(30 m)
(38 m)
(45 m)
(53 m)
94
89
84
74
197
185
175
155
372
349
330
292
763
716
677
600
/
psi (3.5 kPa).
1
2
200 ft
250 ft
(60 m)
(76 m)
67
62
140
129
265
243
543
500
814
749
1,440
/
psi
1
2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nfc-250/200h

Table of Contents