Ref
Description
K
Clearance to a mechanical air supply inlet
Clearance above paved sidewalk or paved
L
driveway located on public property
Clearance under veranda, porch deck, or
M
balcony
1 In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code
2 In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code
† A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings
and serves both dwellings.
‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* Clearance in accordance with local installation codes and the requirements of the gas supplier.
72
Venting for Combustion Air
Canadian Non-Direct
Vent Installations
1
6 ft (1.83 m)
7 ft (2.13 m)
12 in (30 cm)
US Non-Direct Vent
Installations
2
36 in (91 cm) above
if within 10 ft (3 m)
horizontally
*
*