3.6.3 System Application - Zone System with Pumps (Primary/Secondary Piping)
Not to exceed 4 pipe Dia or Max. 12"
Pressure
Air Vent
Relief Valve
System application drawings are intended to explain the system piping concept only.
Note
Install a NaviClean filter in the system return to remove foreign objects from the system. Foreign
objects inside the system may result in abnormal system operation.
Refer to "3.4 Filling the System" on page 32 for make-up water connections and refer to the
requirements of your local codes to ensure compliance.
Use a pump with an integral check valve or install a check valve at the pump outlet.
Refer to "3.7.3 Wiring Diagram - Zone Pump System" on page 46 for wiring connections.
Additional Zone
NaviClean
Air Separator
Zone #2
Zone #1
Backflow
preventer
Pressure
reducing valve
Expansion Tank
Make-up Water
Installing the System Piping
37