Download Print this page

ICT ICT24012-10CM Instruction Manual

Advertisement

Quick Links

PROTECTION FEATURES
Internal circuitry will help protect the load, battery and power
supply in case of the following events:
Internal temperature too high - will reduce output current
until stable temperature maintained
Input ac voltage out of range - will shut off output,
automatically restarts when in operating range
Output Short Circuit – current regulated to less than the
max rated level
Output Over Voltage – will shut off output, automatically
restarts after delay
Battery current too high – dc output fuse will open
Reverse Battery connection – dc output fuse will open
Input Over current – internal AC fuse will open
SPECIFICATIONS
Input Voltage:
100 – 264Vac 50/60Hz
Input Power Factor:
0.99 (120Vac input)
V-output Line Regulation:
+/- 0.1%
V-output Load Regulation:
+/- 0.2%
Electronic current limit:
Constant current regulation with
fold back for short circuit
conditions
Operating Temperature:
-30°C to 60°C
Output Grounding:
Positive, Negative or floating
Efficiency:
88% typical (120Vac)
EMC:
Meets FCC part 15 class B limits
Safety:
Designed to meet EN60950-1
Model:
12V 20A
12V 12A
Output Voltage
(Nominal, +/-
13.8V
13.8V
0.5%)
Continuous
Current Rating
20A
10A
(at nominal
output voltage)
Output Current
20A
12A
Limit (+5%,-0%)
Output V Noise
25 mVrms
25 mVrms
(max)
Input Current
3Aac
1.8Aac
max at 100Vin
Output Power
276W
166W
(max rated)
1
Reduce output current 1% per °C for ambient above 50°C
All manuals and user guides at all-guides.com
LIMITED WARRANTY
ICT Limited Warranty is only intended for the benefit of the original
Purchaser of this product. This Warranty is not transferable or
assignable without the prior written permission of ICT. ICT's sole
obligation and liability under this warranty is limited to either
repairing or replacing defective products at the sole discretion of
ICT. When repairing or replacing the products, ICT may use
products or parts that are new, equivalent to new or re-
conditioned. Parts repaired or replaced during the warranty period
will be under warranty for the remainder of the warranty period.
The warranty period on ICT products purchased new from ICT is
two years. The warranty period for a repaired product or part
thereof is ninety (90) days or the remainder of the unexpired term
of the new product warranty period, whichever is greater. Repair
or replacement of a defective product or part does not extend the
original warranty coverage period.
No claim will be accepted unless written notice of the claim is
received by ICT in accordance with ICT's Return Material
Authorization (RMA) procedure, as soon as reasonably possible
after the defect is discovered. A valid product serial number must
be provided with the RMA claim to prove eligibility. The RMA form
is
available
power.com/support/warranty-repair/.
The Purchaser shall at their own risk and cost return the defective
1
product to ICT's factory or designated repair center once an RMA
is issued by ICT. Return of the products to the customer after
repair is completed shall be prepaid by ICT unless otherwise
mutually agreed between the parties. Products shipped to ICT
which have incurred freight damage will not be covered by this
Warranty and any repairs or replacement parts, components or
products needed will be invoiced in the full current price amount
and returned freight collect to Purchaser. It is the Purchaser's
responsibility to check the product upon receipt for any damage
24V 10A
during shipping and to contact the carrier or shipper regarding
such damage. Product that is returned as defective, which is
determined to operate within published specifications will be
27.6V
returned to the Purchaser freight collect.
This Warranty will be void if the product has been subjected to
misuse, neglect, accident, exposure to environmental conditions
not conforming to the products' limits of operation, improper
10A
installation or maintenance, improper use of an electrical source,
defects caused by sharp items or by impact pressure, a force
majeure event, has been modified or repaired by anyone other
10A
than ICT or its authorized representative, has been subjected to
unreasonable physical, thermal or electrical stress, improper
maintenance, or causes external to the unit including but not
25 mVrms
limited to general environmental conditions such as rust, corrosive
atmospheres, sustained temperatures outside the specified
operating range of the equipment, exposure to power surges
3Aac
and/or electrical surges, improper grounding, mould or dust,
animal or insect damage, water damage or immersion in liquid of
any kind.
276W
ICT does not control the installation and use of any ICT product.
Accordingly, it is understood this does not constitute a warranty of
performance or a warranty of fitness for a particular purpose.
on
the
ICT
website
at
www.ict-
Innovative Circuit
Technology Ltd.
CM Series DC Power
Supply
INSTRUCTION MANUAL
855-159-001
Models:
ICT24012-20CM
ICT24012-12CM
ICT24024-10CM
INNOVATIVE CIRCUIT TECHNOLOGY LTD.
26921 Gloucester Way
Langley, British Columbia, Canada V4W 3Y3
T 604.856.6303 F 604.856.6365
www.ict-power.com

Advertisement

loading

Summary of Contents for ICT ICT24012-10CM

  • Page 1 PROTECTION FEATURES LIMITED WARRANTY Internal circuitry will help protect the load, battery and power ICT Limited Warranty is only intended for the benefit of the original supply in case of the following events: • Purchaser of this product. This Warranty is not transferable or Internal temperature too high - will reduce output current assignable without the prior written permission of ICT.
  • Page 2 • Connect the supply POS output terminal to the load The CM Series off-line power supplies from ICT provide a positive input The unit will now power the load and trickle charge the optional reliable 275 Watts of dc power with a built-in battery back-up •...

This manual is also suitable for:

Ict24012-12cmIct24012-20cm