Omron E5 N-H Series Manual page 53

Digital temperature controllers/digital controllers
Hide thumbs Also See for E5 N-H Series:

Advertisement

External Connections
• A voltage output (control output 1, for driving SSR) is not electrically insulated from the internal circuits. When using a grounding thermocouple,
do not connect any of the control output terminals to ground. If the control output terminals are connected to ground, errors will occur in the
measured temperature values as a result of leakage current.
The voltage output (control output 2, for driving SSR) has basic insulation provided for the internal circuit
Controllers
• 100 to 240 VAC
• 24 VAC/VDC (no polarity)
Control outputs 1, 2
Input power
Output Unit
supply
Control outputs 1, 2
Relay Outputs
250 VAC, 5 A
Control output 1
(resistive load)
SSR Outputs
75 to 250 VAC, 1A
(resistive load)
Control output 2
Models with Position-
proportional Control
250 VAC, 1 A
(including inrush
Auxiliary output 2
current)
Auxiliary outputs 1, 2
Relay output
Auxiliary output 1
SPST-NO,
250 VAC, 3 A
(resistive load)
DO NOT USE
Remote SP input
Note: Wire all voltage input terminals correctly. The Controller may fail if voltage input terminals are wired incorrectly.
Option Units
Event Inputs
1
21
21
11
EV2
2
22
22
12
3
23
23
13
CT2
4
24
24
14
CT1
5
25
25
15
CT2
6
26
26
16
DO NOT
7
27
27
17
USE
DO NOT
8
28
28
18
USE
9
29
29
19
10
30
30
20
21
22
23
EV3
24
EV4
25
26
27
4 to 20 mA DC
Transfer output
(Load: 600 Ω max.)
28
29
4 to 20 mA DC
30
Communications
E53-EN01
E53-EN02
RS-232C
RS-422
11
SD
11
RDB
12
12
RD
RDA
13
13
SG
SG
21
DO NOT USE
21
SDB
22
22
SDA
DO NOT USE
EV1
Potentiometer
O
14
W
15
Auxiliary output 3
16
C
DO NOT
DO NOT
USE
USE
A
DO NOT
V
USE
B
DO NOT
DO NOT
B
USE
USE
E5AN-H/E5EN-H
E53-EN03
RS-485
11
B (+)
11
12
12
A (−)
13
13
DO NOT USE
21
B (+)
21
22
A (−)
22
Auxiliary output 3
Relay output
SPDT, 250 VAC, 3 A
(resistive load)
A heater burnout alarm, SSR
failure, heater overcurrent
alarm, or input alarm is sent
mA
to the output to which the
alarm 1 function is assigned.
E53-AKB
Event Inputs
EV2
EV1
53