Panasonic CS-Z35UFRAW Service Manual page 51

Hide thumbs Also See for CS-Z35UFRAW:
Table of Contents

Advertisement

12.2.6
Pipe Insulation
1
Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation
Diagram. Please wrap the insulated piping end to prevent water from going inside the piping.
2
If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by
using POLY-E FOAM with thickness 6 mm or above.
12.2.6.1
Cutting and Flaring the Piping
1
Please cut using pipe cutter and then remove the burrs.
2
Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused.
Turn the piping end down to avoid the metal powder entering the pipe.
3
Please make flare after inserting the flare nut onto the copper pipes.
Point down
1. To cut
2. To remove burrs
12.2.7
Disposal of Outdoor Unit Drain Water
If a drain elbow is used, the unit should be placed on a stand which is taller than 3 cm.
If the unit is used in an area where temperature falls below 0°C for 2 or 3 days in succession, it is recommended
not to use a drain elbow, for the drain water freezes and the fan will not rotate.
Pipe
Handle
Reamer
Bar
Yoke
Red arrow mark
Clamp handle
3. To flare
Drain elbow
Install the hose at an angle so that the water smoothly flows out
0 – 0.5 mm
Bar
Core
When properly flared, the internal surface of the flare will evenly shine
Copper
and be of even thickness. Since the flare part comes into contact with
pipe
the connections, carefully check the flare finish.
1
Hose
51
Improper flaring
Inclined Surface
Cracked Uneven
damaged
thickness