Fluke i6000s Flex-24 Instruction Sheet page 8

Ac current probe
Table of Contents

Advertisement

To avoid electric shock or injury, the flexible current
Probes are not for use on conductors with a
potential of over 600 V.
2.
Wrap the flexible measuring head around the conductor
to be tested in a close coupling manner.
3.
Energize the circuit under test.
4.
For most accurate measurement, centre the flexible
head around the conductor.
5.
Locate coupling away from the nearby conductors.
To avoid electric shock or injury:
Do not use the flexible current Probes to
measure bare conductors unless wearing
protective clothing suitable for high voltage
work.
Always use appropriate equipment for personal
protection. When installed on bare
conductors/busbars, the product must be within
a suitable enclosure.
Operation
To activate the unit, move the switch from 'Off' position to the
required measuring range. If the value of current being measured
is unknown, select the 6000 A current range and then reduce
accordingly.
XWWarning
WX Warning
Ieb0001.eps