Installation of the inverter
2.3.2
Amount of heat generated by the inverter
Installing the heat sink inside the enclosure
When the heat sink is installed inside the enclosure, the amount of heat generated by the inverter unit is shown in the
following tables.
Inverter FR-A846-[]
00023(0.4K)
00038(0.75K)
00052(1.5K)
00083(2.2K)
00126(3.7K)
00170(5.5K)
00250(7.5K)
00310(11K)
00380(15K)
00470(18.5K)
00620(22K)
00770(30K)
00930(37K)
01160(45K)
01800(55K)
02160(75K)
02600(90K)
03250(110K)
03610(132K)
NOTE
• The amount of heat generated shown assumes that the output current is the inverter rated current, and the carrier frequency
is 2 kHz.
20
INSTALLATION AND WIRING
Amount of heat generated (W)
LD
ND
50
40
70
55
80
70
120
100
160
130
230
170
325
230
370
295
440
400
530
460
700
545
840
705
1060
880
1260
1060
1750
1300
2210
1800
2700
2250
2900
2400
3700
2900

Advertisement