Friedrich Hazardgard SH20M50B Installation & Operation Manual page 6

Hazardous location room air conditioner

Advertisement

Available languages

Available languages

ATEX & ICEX Standards Specific to Models SH20N50AT & SH24N30AT
SH20N50AT and SH24N30AT Adhere to the following certifications:
CERTIFIED
PER STD. NO. ANSI/ISA 12.12.01,2013
PER STD. NO. IEC 60079-0, 6th Edition PER STD. NO. IEC 60079-15, 4th Edition
PER STD. NO. CAN/CSA C22.2 NO. 213-M1987
PER STD. NO. CENELEC EN 60079-0: 2012 + A11: 2013
PER STD. NO. CENELEC EN 60079-15: 2010
CERTIFICATION DEMKO 15 ATEX 1364X
IECEX UL15.0051X
SH20N50AT & SH24N30AT
Specific Conditions of Use:
• Provision shall be made to prevent the rated voltage being exceeded by
the transient disturbances of more than 140% of the peak rated voltage.
• The equipment must be installed only for use in locations providing
adequate protection against the entry of solid foreign objects or water
capable of impairing safety.
• Only permanently wired cables may enter the cable glands. The user
shall provide for the required strain relief.
• Degree of protection will be safeguarded only when sealing and cable
entry fittings are properly fitted. To ensure proper protection, all wiring
connections and conduit passageways must have the appropriate ATEX/
IECEx certified plug or cable gland.
• Cable Glands shall be mounted into the enclosure in such a way that
they are mechanically protected against impact force.
• To avoid the buildup of electrostatic charge, regularly clean the unit with
a damp cloth.
• The appliance is not to be used by persons (including children) with
reduced physical, sensory or mental capabilities, or lack of experience
and knowledge, unless they have been given supervision or instruction.
Children to be supervised not to play with the appliance.
• The enclosure with a coating must not be used in areas affected by
charge-producing processes, mechanical friction and separation
process, electron emission (e.g. in the vicinity of electrostatic coating
equipment), and pneumatically conveyed dust.
The following additional previous editions of Standards noted under the "Standards" section of this
Certificate where applied to integral Components as itemized below. There are no significant safety re-
lated changes between these previous editions and the editions noted under the "Standards" section.
Junction Box, Part No. 25. 10 16
08, manufactured by Rose.
Electrical Ratings:
ATEX/IECEx Model Number
SH20N50AT
SH24N30AT
Refrigerant System Ratings:
ATEX/IECEx Model Number
SH20N50AT-B
SH24N30AT-A
II 3 G Ex ec nA nC IIC T4 Gc
DEMKO 15 ATEX 1364X
IEC 60079-7:2006-
07, IEC 60079-31:
Rated Voltage,
Rated Cooling
Frequency
Amps
240/220, 50Hz
11.6
230/208, 60 Hz
11.8
R-410a Charge, oz
High-Side Design Pressure (PSIG)
40.7
600
46.8
600
NOTICE: To maintain IP44 protection, the Hazardgard
unit must be installed in accordance to the installation
instructions stated in this document.
Compressor
Motor
RLA,LRA
FLA
9.4, 50
2
10.2, 52
1.5
Low-Side Design Pressure (PSIG)
300
300
Motor
MCA
MOP
HP
1/3
13.25
20
1/4
14.25
20