Danfoss VLT HVAC Drive FC100 Service Manual page 131

High power f frames
Table of Contents

Advertisement

Special Test Equipment
Pin
Schemat
No.
ic
Acronym
17
FAN_ON
18
HI_LOW
19
SCR_DIS
20
INV_DIS
21
22
UINVEX
23
VDD
24
VCC
25
GUP_T
10
10
26
GUN_T
27
GVP_T
28
GVN_T
29
GWP_T
130
High Power Service Manual for Modular F Frame Drives
Function
Description
Pulse train to gate SCR's
8.00
for fan voltage control.
6.00
In sync with line freq.
4.00
2.00
0.00 V
-2.00
-4.00
-6.00
-8.00
-4.0ms
7 trigger pulses at 3Khz
Control signal from
Signal to switch fan speeds between high and low
Power Card
Control signal for SCR
Indicates SCR front end is enabled or disabled.
front end
Control signal from
Disables IGBT gate voltages
Power Card
Not used
Bus Voltage scaled
Signal proportional to UDC
down
+24 VDC power supply
Yellow LED indicates voltage is present.
+5.0 VDC regulated
The green LED indicates voltage is present.
supply. +4.75-5.25 VDC
IGBT gate signal,
8.00
buffered, U phase,
6.00
positive. Signal
4.00
originates on Control
2.00
Card.
0.00 V
-2.00
-4.00
-6.00
-8.00
-4.0ms
2v/div 100us/div Run@10Hz
IGBT gate signal,
8.00
buffered, U phase,
6.00
negative. Signal
4.00
originates on Control
2.00
Card.
0.00 V
-2.00
-4.00
-6.00
-8.00
-4.0ms
2v/div 100us/div Run@10Hz
IGBT gate signal,
8.00
buffered, V phase,
6.00
positive. Signal
4.00
originates on Control
2.00
Card.
0.00 V
-2.00
-4.00
-6.00
-8.00
-4.0ms
2v/div 100us/div Run@10Hz
IGBT gate signal,
8.00
buffered, V phase,
6.00
negative. Signal
4.00
originates on Control
2.00
Card.
0.00 V
-2.00
-4.00
-6.00
-8.00
-4.0ms
2v/div 100us/div Run@10Hz
IGBT gate signal,
8.00
buffered, W phase,
6.00
positive. Signal
4.00
originates on Control
2.00
Card.
0.00 V
-2.00
-4.00
-6.00
-8.00
-4.0ms
2v/div 100us/div Run@10Hz
MG90K202 - VLT
Reading Using a Digital Voltmeter
5VDC - fans off
Input A
2ms/Div
+5VDC = fans on high,
Otherwise, 0VDC.
0.6 to 0.8 VDC – SCRs enabled
0VDC – SCR disabled
5VDC – inverter disabled
0VDC – inverter enabled
OV switch must be off
- 1 VDC = 450 VDC [T4/T5]
- 1 VDC = 610 VDC [T7]
+24 VDC regulated supply
+23 to 25 VDC
+5.0 VDC regulated supply +4.75 to 5.25 VDC
2.2–2.5 VDC
Input A
Equal on all phases
TP25-TP30
50Us/Div
2.2–2.5 VDC
Input A
Equal on all phases
TP25-TP30
50Us/Div
2.2–2.5 VDC
Input A
Equal on all phases
TP25-TP30
50Us/Div
2.2–2.5 VDC
Input A
Equal on all phases
TP25-TP30
50Us/Div
2.2–2.5 VDC
Input A
Equal on all phases
TP25-TP30
50Us/Div
®
is a registered Danfoss trademark

Advertisement

Table of Contents
loading

Table of Contents