Danfoss VLT HVAC Drive FC100 Service Manual page 130

High power f frames
Table of Contents

Advertisement

Special Test Equipment
Pin
Schemat
Function
No.
ic
Acronym
22
UINVEX
Bus Voltage scaled
down
23
VDD
+24 VDC power supply
24
VCC
+5.0 VDC regulated
supply. +4.75-5.25 VDC
25
GUP_T
IGBT gate signal,
buffered, U phase,
positive. Signal
originates on Control
Card.
26
GUN_T
IGBT gate signal,
buffered, U phase,
negative. Signal
originates on Control
Card.
27
GVP_T
IGBT gate signal,
buffered, V phase,
positive. Signal
originates on Control
Card.
28
GVN_T
IGBT gate signal,
buffered, V phase,
negative. Signal
originates on Control
Card.
29
GWP_T
IGBT gate signal,
buffered, W phase,
positive. Signal
originates on Control
Card.
30
GWN_T
IGBT gate signal,
buffered, W phase,
negative. Signal
originates on Control
Card.
High Power Service Manual for Modular F Frame Drives
Description
Signal proportional to UDC
Yellow LED indicates voltage is present.
The green LED indicates voltage is present.
Input A
8.00
6.00
4.00
2.00
0.00 V
-2.00
-4.00
-6.00
-8.00
-4.0ms
50Us/Div
2v/div 100us/div Run@10Hz
Input A
8.00
6.00
4.00
2.00
0.00 V
-2.00
-4.00
-6.00
-8.00
-4.0ms
50Us/Div
2v/div 100us/div Run@10Hz
Input A
8.00
6.00
4.00
2.00
0.00 V
-2.00
-4.00
-6.00
-8.00
-4.0ms
50Us/Div
2v/div 100us/div Run@10Hz
Input A
8.00
6.00
4.00
2.00
0.00 V
-2.00
-4.00
-6.00
-8.00
-4.0ms
50Us/Div
2v/div 100us/div Run@10Hz
Input A
8.00
6.00
4.00
2.00
0.00 V
-2.00
-4.00
-6.00
-8.00
-4.0ms
50Us/Div
2v/div 100us/div Run@10Hz
Input A
8.00
6.00
4.00
2.00
0.00 V
-2.00
-4.00
-6.00
-8.00
-4.0ms
50Us/Div
2v/div 100us/div Run@10Hz
®
MG90K202 - VLT
is a registered Danfoss trademark
Reading Using a Digital Voltmeter
OV switch must be off
- 1 VDC = 450 VDC [T4/T5]
- 1 VDC = 610 VDC [T7]
+24 VDC regulated supply
+23 to 25 VDC
+5.0 VDC regulated supply +4.75 to 5.25 VDC
2.2–2.5 VDC
Equal on all phases
TP25-TP30
2.2–2.5 VDC
Equal on all phases
TP25-TP30
2.2–2.5 VDC
Equal on all phases
TP25-TP30
2.2–2.5 VDC
Equal on all phases
TP25-TP30
2.2–2.5 VDC
Equal on all phases
TP25-TP30
2.2–2.5 VDC
Equal on all phases TP25-TP30
10
10
129

Advertisement

Table of Contents
loading

Table of Contents