Cleaning the Condensate Trap (Siphon)
The Trap is located inside the boiler but is removed from below the boiler
First remove the condensate drain line then remove/unscrew the SRD Device (if appli-
cable)
2/ Remove the C shaped trap tetainer by removing the philips securing screw
3/ With a towel below turn the trap half a turn and pull out the trap (Take care as it
should be full of water )
4/ Clean the siphon, it can be washed with detergent water.
Wash the SRD device out thoroughly (
or residues inside the device, as they could damage it.)
After the cleaning reassemble the siphon and the SRD device, taking care to fit
the components with care.
Gap 6mm +/- 1mm
Fig A1
Combustion fan check valve (Fig. 22)
The boiler has a combustion inlet check valve between the fan and inlet conveyor
To access the check valve:
1/ Remove the fan by unscrewing the 4 screws fixing it to the conveyor
As you remove it take great care to note which way around the check device it is
fitted
2/ Make sure there are no foreign material deposits on the membrane of the check
valve and if present remove them check for damage and that the valve opens and
closes correctly
Re-assemble the components in reverse order, making sure it is put
the correct direction.
These Minimum service requirements for Mynute X boilers are a requirement of warranty
For the safety of the user, Service should be carried out throughout the life of the appliance.
X
Mynute
Boilers : Service requirements
Never use metal or pointed tools to remove deposits
Ignition electrode
Ionization electrode
back in
Check
valve