Front Cover
Support fitted
into its base
IMPORTANT! All wiring is done with the cover open, as shown above. The front cover support fits into its base.
Make sure the support is up before closing the front cover.
Wireless Ethernet Connection
Current
Electronic Circuits
Inputs
Ia Ia Ib Ib Ic Ic
(+) (-) (+) (-) (+) (-)
Va Vb Vc Vn L1 L2 PE
Voltage
Inputs
Access Holes for
Wiring
Select wiring diagram to meet your application. See User Manual for additional wiring diagrams.
LINE
N
C
B
A
CT
Shorting
Block
Earth Ground
FUSES
3 x 0.1A
N
C
B
A
LOAD
Electro Industries/GaugeTech
Powered by Innovation™
circuits can, at times, produce lethal voltages and currents. Avoid
contact with any current-carrying surfaces. Before performing ANY
work on the Shark® 100S/200S meter, make sure the meter is
powered down and ALL circuits are de-energized.
AVERTISSEMENT! Pendant le fonctionnement normal du compteur
Shark® 100S/200S des tensions dangereuses suivant de nombreuses
pièces, notamment, les bornes et tous les transformateurs de courant
branchés, les transformateurs de tension, toutes les sorties, les entrées
et leurs circuits. Tous les circuits secondaires et primaires peuvent
parfois produire des tensions de létal et des courants. Évitez le contact
avec les surfaces sous tensions. Avant de faire un travail dans le
compteur, assurez-vous d'éteindre l'alimentation et de mettre
tous les circuits branchés hors tension.
Ethernet, RJ45
Jack
JP2
RS485 Output
(Do not put the
Voltage on these
terminals!)
RS485
KYZ Pulse
Output
Power Supply
Detail of JP2 Board and
Inputs (Inputs
are unipolar)
Electronic Circuits
Ia+ Ia-
Ib+ Ib-
Ic+ Ic-
CN2
CN1
Va
Vb
Vc
Vref
L1
L2
PE
Power
Supply
Connection
WYE Direct, 3
Phase, 4 Wire
WARNING!
During normal operation of the meter
dangerous voltages flow through many parts of the meter,
including Terminals and any connected CTs and PTs, all I/O
modules and their circuits. All Primary and Secondary
NOTE: Jumper 2 (JP2) must be set for
either RS485 or Ethernet communica-
tion (see figures on the left for location
of JP2 and settings). Put the jumper on
positions 2 and 3 for LAN (Ethernet)
communication, or on 1 and 2 for
RS485 communication.
Location of JP2
Enlargement of JP2,
Showing Settings
LAN/485 Setting
LINE
N
C
B
A
CT
Shorting
Block
Earth Ground
FUSES
3 x 0.1A
Earth Ground
N
C
B
A
LOAD
Doc
#
E145723
Shark® 100S/200S Quickstart
Electronic Circuits
Ia+ Ia-
Ib+ Ib-
Ic+ Ic-
CN2
CN1
Va
Vb
Vc
Vref
L1
L2
PE
Power
Supply
Connection
WYE with PTs, 3
Phase, 4 Wire
V.1.16
QS - 2

Advertisement

loading

This manual is also suitable for:

Shark 200s