Table 16-4 Alert Codes
Code
Description
249
CH ODR time of day setpoint was invalid
250
CH ODR time of day set point exceeds normal set point
251
CH max outdoor set point was invalid
252
CH min outdoor setp oint was invalid
253
CH min water set point was invalid
254
CH outdoor temperature range was too small (minimum 12 C / 22 F)
255
CH water temperature range was too small (minimum 12 C / 22 F)
CH ODR min water temperature was invalid
259
260
RESERVED
261
DHW set point was invalid
262
DHW time of day set point was invalid
DHW storage setpoint was invalid
263
264
STAT may not be a DHW demand source when Remote Stat is enabled
265
No DHW anticondensation setpoint was configured
266
No CH anticondensation setpoint was configured
267
STAT may not be a CH demand source when Remote Stat is enabled
268
CH 4mA water temperature setting was invalid
269
CH 20mA water temperature setting was invalid
270
Steam 4mA water temperature setting was invalid
271
Steam 20mA water temperature setting was invalid
272
Abnormal Recycle: Pressure sensor fault
273
Abnormal Recycle: Safety relay drive test failed
274
Abnormal Recycle: Demand off during Pilot Flame Establishing Period
275
Abnormal Recycle: LCI off during Drive to Purge Rate
276
Abnormal Recycle: LCI off during Measured Purge Time
277
Abnormal Recycle: LCI off during Drive to Light off Rate
278
Abnormal Recycle: LCI off during Pre-Ignition test
279
Abnormal Recycle: LCI off during Pre-Ignition time
280
Abnormal Recycle: LCI off during Main Flame Establishing Period
281
Abnormal Recycle: LCI off during Ignition period
282
Abnormal Recycle: Demand off during Drive to Purge Rate
283
Abnormal Recycle: Demand off during Measured Purge Time
284
Abnormal Recycle: Demand off during Drive to Light off Rate
285
Abnormal Recycle: Demand off during Pre-Ignition test
286
Abnormal Recycle: Demand off during Pre-Ignition time
287
Abnormal Recycle: Flame was on during Safe Start check
288
Abnormal Recycle: Flame was on during Drive to Purge Rate
289
Abnormal Recycle: Flame was on during Measured Purge Time
290
Abnormal Recycle: Flame was on during Drive to Light off Rate
291
Abnormal Recycle: Flame was not on at end of Ignition period
292
Abnormal Recycle: Flame was lost during Main Flame Establishing Period
293
Abnormal Recycle: Flame was lost early in Run
294
Abnormal Recycle: Flame was lost during Run
295
Abnormal Recycle: Leakage test failed
296
Abnormal Recycle: Interrupted air flow switch was off during Drive to Purge Rate
297
Abnormal Recycle: Interrupted air flow switch was off during Measured Purge Time
298
Abnormal Recycle: Interrupted air flow switch was off during Drive to Light off Rate
299
Abnormal Recycle: Interrupted air flow switch was off during Pre-Ignition test
300
Abnormal Recycle: Interrupted air flow switch was off during Pre-Ignition time