NTI Trinity Tft399 Installation And Operation Manual page 45

Hide thumbs Also See for Trinity Tft399:
Table of Contents

Advertisement

Tft Series
Table 10-4 Circulator and Pipe Size Requirements
Temp.
Boiler Flow
Model
Rise (ºF)
Rate (GPM)
20
Tft60
25
35
20
Tft85
25
35
20
Tft110
25
35
20
Tft154
25
35
20
Tft201
25
35
20
Tft285
25
35
20
Tft340
25
35
20
Tft399
25
35
Notes:
1
Pump sizing based on Primary/Secondary plumbing configuration with specified minimum pipe diameter with up to 50'
equivalent length.
2
Upsize piping to 1-1/4" if using Armstrong Astro 30 or B&G NRF-22; alternatively upsize circulator to Astro 50 or NRF-
25.
Boiler Head
Minimum
Loss (ft)
Pipe Size
6
2.7
4
1.6
3
1.0
8
3.4
6
2.7
4
1.6
10
3.9
8
3.4
6
2.7
14
5.3
11
3.9
8
3.1
18
7.5
15
5.8
11
3.9
26
14
21
9.8
15
5.7
32
7.9
25
8.2
18
5.7
37
8.2
29
5.7
21
3.9
Installation and Operation Instructions
Minimum Primary Loop Pump Size
B&G
Grundfos
1"
NRF-22
UPS15-58
¾"
NRF-22
UPS15-58
¾"
NRF-9
UPS15-58
1"
NRF-22
UPS15-58
1"
NRF-22
UPS15-58
¾"
NRF-22
UPS15-58
1"
2
2
NRF-22
UPS15-58
1"
NRF-22
UPS15-58
1"
NRF-22
UPS15-58
1-1/4"
NRF-25
UPS26-99
1-1/4"
NRF-22
UPS15-58
1"
NRF-22
UPS15-58
1-1/2"
NRF-36
UPS26-99
1-1/4"
NRF-36
UPS26-99
1-1/4"
NRF-22
UPS15-58
1-1/2"
NRF-36
UPS26-99
1-1/2"
NRF-36
UPS26-99
1-1/4"
NRF-25
UPS26-99
2"
NRF-36
UPS26-99
1-1/2"
NRF-36
UPS26-99
1-1/2"
NRF-36
UPS26-99
2"
PL55
UPS26-150
2"
NRF-36
UPS26-99
1-1/2"
NRF-36
UPS26-99
Trinity
(1)
Taco
Armstrong
0015-MS
Astro 30
0015-MS
Astro 30
0015-MS
Astro 30
0015-MS
Astro 30
0015-MS
Astro 30
0015-MS
Astro 30
2
0015-MS
Astro 30
0015-MS
Astro 30
0015-MS
Astro 30
0015-MS
E7
0015-MS
Astro 30
0015-MS
Astro 30
0013-MS
E7
0013-MS
E7
0015-MS
Astro 30
0013-MS
E8
0013-MS
E7
0015-MS
E7
0012-MS
E8
0013-MS
E7
0013-MS
E7
2400-60
E11
0012-MS
E8
0013-MS
E7
45