Tft Series
Dirt Removal – A dirt removal device should be installed in all systems. In older systems containing cast iron
radiators/baseboard or large amount black iron or steel pipe a magnetic dirt separator must be installed.
Glycol, Snow Melt, and Oxygen Permeable Piping – When freeze protection is required, only multi metal
inhibited propylene glycol, at a minimum of 20% and a maximum of 50%, is allowed for use with boiler
system. If the boiler is being used with a snow melt system that requires a concentration of glycol higher
than 50%, then a plate heat exchanger is required to separate the snow melt system from the boiler water.
Note: the use of glycol may reduce the usable output capacity of the boiler, thus requiring the unit to be
"down-fired" by limiting the maximum operating capacity and/or the maximum water temperature. If
oxygen permeable piping (non-oxygen barrier tubing) is used in the system a plate heat exchanger is required
to separate it from the boiler water.
Ethylene glycol is prohibited for use with the boiler, only inhibited propylene glycol is
allowed for use with the boiler.
Water Treatment – When filling the boiler system, the water must be tested. Table 10-1 outlines the
parameters that should be tested for, and the corresponding ranges that are permitted. Water quality that does
not fall within the stated ranges will void the warranty of the boiler. Utilize proper testing equipment, such as
digital meters, to verify water quality.
Never use petroleum based compounds in the system for cleaning or sealing.
Inhibitors should be used for all installations in both new and existing heating systems. Follow the
instructions provided by the inhibitor manufacturer when adding it to the system to ensure the correct
concentration. A list of approved inhibitors is provided below.
Rhomar Pro-tek 922
Sentinel X100
Fernox Protector F1
Table 10-1 Boiler System Cleansers and Corrosion Inhibitors
Parameter
pH
Conductivity
Hardness
Chlorine
Glycol (if applicable)
Total Dissolved Solids (TDS)
Bacteria/Mold
Molybdate Corrosion Inhibitor
Installation and Operation Instructions
Range
Information
The total pH scale ranges from 1 to 14, with 7 considered to
7 to 9
be neutral. A pH less than 7 is said to be acidic and solutions
with a pH greater than 7 are basic or alkaline.
Conductivity is an indirect method of determining the total
dissolved solids in the water. High conductivity in untreated
100 to 300 μS/cm
water indicates hard water. Adding corrosion inhibitors will
increase conductivity.
Artificially soft water can damage the system. The use of un-
50 to 200 ppm
softened water is recommended. Do not use distilled or
(3 to 11.7 gpg)
purified water.
High Chlorine content in the water can damage the boilers
150 ppm
heat exchanger.
Concentrations below 20% can promote bacteria growth, and
concentrations above 50% will dramatically reduce
20-50%
efficiency and may require de-rating the boiler. Inhibited
glycol mixed at 50% should have a pH 8-9. Check with
glycol manufacturer.
TDS includes calcium and magnesium associated with lime scale
50 to 300 ppm
but also includes other harmful solids such as magnetite, chlorides,
sodium and other organic and inorganic materials.
none
Glycol above 20% will kill any bacteria.
100 to 300 ppm
Film-forming inhibitor that protects against iron corrosion.
Trinity