Appendix 2
(Standard to comply with: UL 508C, CSA C22.2 No.274-13)
 General precaution
CAUTION - Risk of Electric Shock -
The bus capacitor discharge time is 10 minutes. Before starting wiring or inspection, switch power off, wait for more than 10 minutes, and check for residual
voltage between terminal P/+ and N/- with a meter etc., to avoid a hazard of electrical shock.
ATTENTION - Risque de choc électrique -
La durée de décharge du condensateur de bus est de 10 minutes. Avant de commencer le câblage ou l'inspection, mettez l'appareil hors tension et attendez plus
de 10 minutes.
 Installation
The below types of inverter have been approved as products for use in enclosure and approval tests were conducted under the following conditions.
Design the enclosure so that the surrounding air temperature, humidity and ambience of the inverter will satisfy the specifications. (Refer to
 Branch circuit protection
For installation in the United States, Class T, Class J, Class CC, or Class L fuses, UL 489 Molded Case Circuit Breaker (MCCB), or Type E combination motor
controller must be provided, in accordance with the National Electrical Code and any applicable local codes.
For installation in Canada, Class T, Class J, Class CC, or Class L fuses, UL 489 Molded Case Circuit Breaker (MCCB), or Type E combination motor
controller must be provided, in accordance with the Canadian Electrical Code and any applicable local codes.
For the FR-A820 series, Class T, Class J, or Class CC fuses, or UL 489 Molded Case Circuit Breaker (MCCB), or Type E combination motor controller must
be provided.
FR-A820-[ ]-GN
Rated fuse voltage (V)
Fuse allowable rating
(A)
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)
Type E combination
motor controller

FR-A820-[ ]-GN
Rated fuse voltage (V)
Fuse allowable rating
(A)
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)
Type E combination
motor controller
FR-A840-[ ]-GN
Rated fuse voltage (V)
Fuse allowable rating
(A)
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)
Type E combination
motor controller

FR-A840-[ ]-GN
Rated fuse voltage (V)
Fuse allowable rating
(A)
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)
Type E combination
motor controller

Maximum allowable rating by the US National Electrical Code. Exact size must be chosen for each installation.

Select an appropriate molded case circuit breaker with a rating that is suitable for the size of the cable.

For UL/cUL certification, use the following product.
MMP-T32

Suitable for Use in a Circuit Capable of Delivering Not More Than 50 or 25 kA rms Symmetrical Amperes, 480Y/277 Volts Maximum when protected by the Type E
Combination motor Controllers indicated in the above table.

Type E combination motor controller is combination of Manual motor starter, Short-circuit Display Unit "UT-TU" and Power Side Terminal Cover Kit "UT-CV3".
Downloaded from
ManualsNet.com
Instructions for UL and cUL
00046
00077
(0.4K)
(0.75K)
240 V or more
Without power factor
15
20
improving reactor
With power factor improving
15
20
reactor
15
15

Maximum current rating (A)
8
13
Maximum SCCR (kA)
50
50

00930
01250
(18.5K)
240 V or more
Without power factor
225
300
improving reactor
With power factor improving
200
250
reactor
225
300

Maximum current rating (A)
Maximum SCCR (kA)
00023
00038
(0.4K)
(0.75K)
500 V or more
Without power factor
6
10
improving reactor
With power factor improving
6
10
reactor
15
15

Maximum current rating (A)
4
6.3
Maximum SCCR (kA)
50
50

00930
01160
(37K)
500 V or more
Without power factor
200
250
improving reactor
With power factor improving
175
200
reactor
225
250

Maximum current rating (A)
Maximum SCCR (kA)
Model
Manufacturer
Mitsubishi Electric Corp.
search engine
00105
00167
00250
00340
(1.5K)
(2.2K)
(3.7K)
(5.5K)
30
40
60
80
20
30
50
70
25
40
60
80
18
25
32
50
25
25
01540
01870
02330
03160
(22K)
(30K)
(37K)
(45K)
(55K)
350
400
500
500
300
350
400
500
350
450
500
700
00052
00083
00126
00170
(1.5K)
(2.2K)
(3.7K)
(5.5K)
15
20
30
40
10
15
25
35
15
20
30
40
8
13
18
25
50
50
50
25
01800
02160
02600
03250
(45K)
(55K)
(75K)
(90K)
(110K)
300
250
300
350
400
450
450
500
Rated Voltage, Vac
480Y/277
00490
00630
00770
(7.5K)
(11K)
(15K)
150
175
200
125
150
200
110
150
190
03800
04750
(75K)
(90K)
600
700
900
1000
00250
00310
00380
00470
(7.5K)
(11K)
(15K)
(18.5K)
70
80
90
110
150
60
70
90
100
125
60
70
90
100
150
32
25
03610
04320
04810
05470
(132K)
(160K)
(185K)
(220K)
500
600
700
800
900
Appendix
page
3.)
00620
00770
(22K)
(30K)
175
150
175
06100
06830
(250K)
(280K)
1000
23

Advertisement

loading