Download Print this page
PDK Red 4 Quick Start Manual

PDK Red 4 Quick Start Manual

Door controller

Advertisement

Quick Links

1. Package Contents
Can Lock (1)
Red 4
Four Door Controller (1)
Battery Leads (1)
Jumpers (8)
4. Input A / DPS Connection
POWER
HEART
B
LINK
A
DPS Contact
Double
DPS Contact
BATTERY
A
DPS (Door Position Switch)
- The DPS is mounted on the door frame in the
desired location with a 22/2 wire running from the DPS to the controller.
Wire the DPS to the controller as shown above. When using two DPS sensors
for double doors, you will wire them in series with only two conductors
running back to the controller for connection.
B
AUX Input
- A rule can be set up to trigger events or outputs based on this
input trigger.
Diode (4)
POE OUT
POE IN
12-24
A
Maglock
Exit) at the door for free egress. Run an 18/2 wire from the Maglock to the
Door Controller, connecting to the Maglock as shown.
REX (Request to Exit)
B
18/5 wire ran from the REX to the controller. Wire the REX to the controller
and Maglock, as shown above. If reporting is not needed in the system, simply
eliminate the green-labeled wire.
C
Jumper Block(s)
If the jumper is off, the relay is a standard dry contact needing input into
common.
AUX Input
2. Mounting Controller
POWER
HEART
LINK
POE OUT
POE IN
BATTERY
12-24
Mount
-
Mount the Red 4 enclosure securely to a wall.
5. Input B / REX Connection
POWER
HEART
LINK
A
Maglock
-
+
BUS
C
If using a powered REX,
run to any 12VDC output
on controller.
B
REX
BATTERY
When installing a Maglock, it is typical to install a REX (Request to
-
-
The REX is mounted in the desired location with an
Use to designate (+) or (-) board voltage out of NO and NC.
-
-
A rule can be set up to trigger events or outputs based on this input trigger.
3. Reader Connection
A
A
Reader(s)
+ -
0 1 L
A
Reader(s)
- Use a 22/5 or 22/6 wire to wire the reader to the controller, as
shown above. Be sure to check polarity and voltage prior to powering the
controller.
B
OSDP
- Place jumper to enable OSDP (see OSDP reference guide at the end
of this guide for more info)
POE OUT
POE IN
12-24
A
Diode
- The provided diode must be installed when using a strike. Install at
the strike with the grey stripe of the diode on positive and the black on
negative.
B
NC
- Used for maglocks (or strikes in fail-safe configuration). Connect the
negative (-) of the maglock or strike to NC on the door controller.
C
NO
- Used for strikes in fail-secure configuration. Connect the negative (-) of
the strike to NO on the door controller.
Jumper Block
D
- Use to designate (+) or (-) board voltage out of NO and NC. If
the jumper is off, the relay is a standard dry contact needing input into
common.
POWER
HEART
LINK
POE OUT
POE IN
BATTERY
12-24
+
OSDP
B
OSDP
Wiring
6. Locking Relay
D
PORT1
PORT2
+
-
+
-
OSDP
BUS
OSDP
BUS
+ -
-
+ -
-
0 1 L
A
B
NC
C
NO
0 1 L
A
B
NC
C
NO
B
C
OR
-
+
BUS
A
A
A

Advertisement

loading
Need help?

Need help?

Do you have a question about the Red 4 and is the answer not in the manual?

Questions and answers

Summary of Contents for PDK Red 4

  • Page 1 Jumpers (8) Diode (4) Mount Mount the Red 4 enclosure securely to a wall. OSDP - Place jumper to enable OSDP (see OSDP reference guide at the end of this guide for more info) 4. Input A / DPS Connection 5.
  • Page 2 Reference Guide OSDP Reference Guide Fire Input - To integrate the fire system using a Red 4 door controller, refer to What is OSDP - Open Supervised Device Protocol (OSDP) is an access control communications standard developed by the Security Industry Association to wiring diagrams in the Partner Portal at prodatakey.zendesk.com...