v.1.0
ADOC 13,8V/3A/OC
Enclosed buffer switch mode power supply unit
with automatic operation control.
EN
Edition: 1 from 29.10.2013
Supercedes edition: ---------------

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ADOC551230 and is the answer not in the manual?

Questions and answers

Summary of Contents for Pulsar ADOC551230

  • Page 1 ADOC551230 v.1.0 ADOC 13,8V/3A/OC Enclosed buffer switch mode power supply unit with automatic operation control. Edition: 1 from 29.10.2013 Supercedes edition: ---------------...
  • Page 2: Table Of Contents

    ADOC551230 Features: 13,8VDC/3A uninterrupted supply FPS technical output indicating PSU failure   – OC and relay type wide range of supply voltage 88÷264VAC  FLB technical output indicating battery low   high efficiency 71% voltage battery charge and maintenance control ...
  • Page 3: Block Diagram

    ADOC551230 1.2 Block diagram. (fig.1). Fig.1. Block diagram of the PSU. 1.3 Description of PSU components and connectors. Table 1. Elements of the PSU (see fig. 2). Element no. Description LED indicating presence of AC power LED indicating presence of DC power LED indicating correct battery voltage FAC- AC absence technical output –...
  • Page 4: Specifications

    ADOC551230 Fig. 2. The view of the PSU. 1.4 Specifications: - electrical specifications (tab.2) - mechanical specifications (tab.3) - operation safety (tab.4) - operating specifications (tab.5) Electrical specifications (tab. 2). Mains supply 88 ÷ 264V AC Current consumption 1A@230VAC typ.
  • Page 5: Installation

    ADOC551230 Temperature characteristics. Chart 1. Acceptable output current from the PSU depending on ambient temperature. Mechanical specifications (tab. 3). Enclosure dimensions 159 x 97 x 38+23 [mm] (LxWxH)(+/- 2) Net/gross weight 0,57kg / 0,61kg Connectors power supply Φ0,64÷1,63 technical outputs: Φ0,41÷1,63 Operation safety (tab.4).
  • Page 6: Installation Procedure

    ADOC551230 2.2. Installation procedure. 1. Before installation of the power supply unit, make sure that 230VAC power if cut off. 2. Mount the unit in the intended location. 3. Connect the 230VAC power cables. Connect the PE cable (yellow-green) to an appropriate PSU terminal (marked with - earth symbol).
  • Page 7: Technical Outputs

    ADOC551230 - green LED (Fig.2, element 3) indicates battery voltage level. Under normal status (U > 11,5V) the diode is permanently illuminated. In case of decrease of battery voltage (U < 11,5V) the diode is off. 3.2 Technical outputs The PSU has indication outputs: ...
  • Page 8 WEEE separately. GENERAL WARRANTY CONDITIONS 1. Pulsar K. Bogusz Sp.j. (the manufacturer) grants a five -year warranty for the equipment, counted from the device’s production date. 2. The warranty includes free-of-charge repair or replacement with an appropriate equivalent (the selection is at the manufacturer’s discretion) if the malfunction is due to the manufacturer, includes manufacturing or material defects, unless such...