CLIFC FIXED - INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Maintenance (Cont'd.)
CONTROLS, PCBS AND WIRIN
The controls and electrical connections should be checked regularly.
The mains power supply connection should be visually checked. If there is any evidence whatsoever of damage or
deterioration of the power supply connection, then the unit must not be put back into service until the supply con-
nection has been replaced by suitably qualified personnel.
The condition of the controls devices, terminals, PCB and any associated wiring should be checked by visual in-
spection.
Any signs of discolouration, arcing or charring of any component, wire or terminal block should be investigated
immediately, and the equipment must not be returned to service until the problem has been found and rectified.
PCBs incorporate fusible links which protect certain components. In the event of a blown fuse, only new fuses of
equivalent specification, size and rating must be used.
The correct fuse ratings are permanently shown on the PCB. If fuses are blowing persistently, this condition must
be investigated immediately, and the equipment must not be returned to service until the problem has been found
and rectified
SERVICE
In order to maximize the useful life of the equipment and keep it operating in good order, the maintenance
checks and tasks detailed in these instructions should be performed as part of a regular and routine ser-
vice s chedule. Under normal operating conditions, the following schedule is recommended:
Spares parts are available by contacting Clima-Flex main sales offic e. Enquiries should include details of the unit
reference and contract number. which will be displayed on the identific ation label.
Alternatively, details of the product and the model can be found on the rating plate
At the end of their useful life. the product. components and pac kaging should be disposed of via a suitable recycling
facility.
Do not dispose of any part of the product. components or packaging with normal household waste. Do not bum.
Item
Filters
Hex Coils
Condensate drip
tray and drains
Fans
Internal / External
surfaces
Controls/ PCO
/ Fuses
18
Maintenance Frequency Program
Monthly
Every 3 months
Inspect / Maintain
Every 6 months
Every 12 months
Inspect / Maintain
Inspect / Maintain
Inspect / Maintain
Inspect / Maintain
Inspect / Maintain