State Water Heaters 310C Installation Manual And Owner's Manual page 17

On-demand water heater
Table of Contents

Advertisement

1 ft. (30 cm)
min.
1 ft.
(30 cm)
min.
Concentric
termination
Concentric wall terminals should
be at least 2 ft. (61 cm) away
from an opposite surface/wall.
Do not place the termination
directly in front of an opening
.
into a building
A
A: In accordance with local codes
For multiple-unit rooftop terminations, space all exhaust and intake terminations in accordance with local
codes. An exhaust termination must be spaced from a wall or surface in accordance with local codes as
well. In the absence of such a code, an exhaust termination must be a horizontal distance of at least 2 ft.
(61 cm) away from a wall or surface.
Please follow all local and national codes in regards to proper termination
clearances. In the absence of such codes, the above clearances can be used as
guidelines. Local codes supersede these guidelines EXCEPT in cases where they
are less restrictive. In such cases, the minimum clearances listed in this manual
CAUTION
must be maintained.
-For sidewall terminations-
For multiple-unit, concentric wall terminals space each
2 ft.
concentric wall terminal at least 1 ft. (30 cm) away from
(61 cm)
min.
each other, no matter the orientation. A concentric wall
terminal must also be at least 2 ft. (61 cm) away from an
inside corner. (If the adjacent wall is less than 2 ft. (61 cm)
of length, the minimum required distance away from the
inside corner will be equal to the length of that adjacent
wall.)
Inside
corner
(61 cm)
-For rooftop terminations-
A
A
Air intake
Exhaust termination
17
Sold by www.GadgetsGo.com Authorized Dealer
3 ft. (91 cm) min.
Concentric wall terminals should
2 ft.
be at least 3 ft. (91 cm) away from
a ventilated or unventilated soffit
min.
2ft.
(61 cm)
min.
Exhaust
termination
Page
Installation Manual
Installation
.
A
A
Air intake