Bryant 987MB Installation, Start-Up, Operating And Service And Maintenance Instructions page 55

Table of Contents

Advertisement

987MB: Installation, Start-up, Operating and Service and Maintenance Instructions
than one click per second until you obtain the required manifold
pressure, see
Fig.
64.
Fig. 64 – Gas Valve without Tower Pressure Ports
10. Main burner flame should be clear blue, almost transparent.
11. After adjusting the Maximum Heat manifold pressure, remove
jumpers across thermostat connections to terminate the call for
heat.
12. Wait for blower off-delay to finish then reset 115-v power to
furnace.
Adjust Manifold Pressure - Minimum Heat
To adjust manifold pressure to obtain input rate for Minimum Heat:
1. Turn SW1-2 ON and SW4-2 must be OFF.
2. Jumper R and W/W1 thermostat connections on control to start
furnace.
3. After the main burners ignite and the blower starts, confirm
Minimum Heat manifold pressure is correct, based on the manifold
pressure tables in the installation instructions.
4. To adjust the Minimum Heat manifold pressure, slowly turn
adjusting screw counterclockwise to decrease manifold pressure or
clockwise to increase manifold pressure. Turn adjustment no more
than one click per second until you obtain the required manifold
pressure, see
Fig.
64.
5. After adjusting the manifold pressure, remove jumpers across
thermostat connections to terminate the call for heat. Wait until the
blower off delay is completed.
6. Move setup switch SW1-2 to the OFF position.
WARNING
!
FIRE HAZARD
Failure to follow this warning could result in personal injury, death,
and/or property damage.
Manifold pressure tap set screw must be tightened and ⅛-in. NPT pipe
plug must be installed to prevent gas leaks.
Clocking The Meter
Verify natural gas input rate by clocking meter.
NOTE: Contact your HVAC distributor or gas supplier for metric gas
meter Tables, if required.
1. Turn off all other gas appliances and pilots served by the meter.
2. Move setup switches SW1-2 to ON position and SW4-2 to OFF.
This keeps furnace locked in low--heat operation when only W/W1
is energized or high heat operation when R to W/W1 and W2 are
jumpered.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
3. Jumper R to W/W1 and W2. Run furnace for 3 minutes in
maximum heat operation.
4. Measure time (in sec) for gas meter to complete one revolution and
note reading. The 2 or 5 cubic feet dial provides a more accurate
measurement of gas flow.
5. Refer to
Table 17
ft./hr by heating value (BTUh/cu ft.) to obtain input rate.
6. If clocked rate does not match required input from Step 5, increase
manifold pressure to increase input or decrease manifold pressure
to decrease input. Repeat steps 3 through 5 until correct maximum
heat input is achieved. See
NOTE: Setup switches SW1-2 must be ON and SW4-2 must be OFF.
This keeps furnace locked in minimum heat operation when R to W/W1
is energized. Repeat items 3 through 6 for minimum heat operation until
minimum heat input is achieved.
7. Remove jumpers across thermostat connections to terminate the
call for heat. Wait until the blower off delay is completed then reset
115-v power to furnace.
A10496
8. Restore furnace to normal operating condition.
9. Remove jumpers across thermostat connections to terminate the
call for heat. Wait until the blower off delay is completed.
10. Disconnect 115 VAC power to furnace.
11. Turn gas valve ON/OFF switch to OFF.
12. Remove water column manometer or similar device from manifold
pressure tap.
FIRE HAZARD
Failure to follow this warning could result in personal injury, death,
and/or property damage.
Manifold pressure tap set screw must be tightened or ⅛-in. NPT pipe
plug must be installed to prevent gas leaks.
13. Tighten set screw on manifold tower pressure tap with 3/32-in hex
wrench, or if 1/8-in. NPT plug was removed, apply pipe dope
sparingly to end of plug and reinstall in the gas valve.
14. Turn gas valve ON/OFF switch to ON.
15. Move setup SW1-2 on furnace control to position required for
attached thermostat (OFF for single-stage thermostats, ON for
two-stage thermostats).
16. Check for gas leaks and verify furnace operation.
.
Table 17 – Gas Rate (CU ft./hr)
SIZE OF TEST DIAL
SECONDS
FOR 1 REV
1 Cu
Ft.
10
360
11
327
12
300
13
277
14
257
55
for cubic ft. of gas per hr. Multiply gas rate cu
Fig.
59.
Burner Flame
Burner
Manifold
Fig. 65 – Burner Flame
WARNING
!
SECONDS
FOR 1 REV
2 Cu
5 Cu
1 Cu
Ft.
Ft.
720
1800
50
655
1636
51
600
1500
52
555
1385
53
514
1286
54
A11461
SIZE OF TEST
DIAL
2 Cu
5 Cu
Ft.
Ft.
Ft.
72
144
360
71
141
355
69
138
346
68
136
340
67
133
333