Manual Bypass Operation
STEP 3. Part A: When the output is coming from the Primary UPS
and the Secondary UPS needs repair, press the Secondary
UPS system's OFF button, if the UPS is powered, until you
hear a beep and see a "STANDBY MODE" message shown
in the LCD display.
Part B: When the output is coming from the Secondary
UPS and the Primary UPS needs repair, press the Primary
UPS system's OFF button, if the UPS is powered, until you
hear a beep and see a "STANDBY MODE" message shown
in the LCD display.
Part C: When both power modules show output is in
Bypass, set the Maintenance Breaker Switch to the ON
position before servicing.
STEP 4. Disconnect any external battery module(s) from the UPS
power module being serviced.
STEP 5. At the rear of the UPS being serviced, remove the 2
screws that secure the PDU to the power module. If
both power modules are in need of service, remove all 4
screws.
STEP 6. Remove the rackmounting hardware from the front panel
of the UPS. Using an assistant at each end, carefully pull
the power module away from the PDU, being careful not
to disconnect the parallel cable. Once the power module
is pulled from the PDU and powers down, disconnect the
parallel cable from the power module.
The UPS power/battery module is now safely powered down and it can be detached from the PDU to perform maintenance/
replacement.
During this process, ensure that each section is properly supported after they are separated. If the sections are detached in a rackmount
application, be sure that each section remains adequately supported by the UPS system's rackmount rails. If the sections are detached in a
tower application, be sure that the PDU is supported by the UPS system's tower feet. Adjust the tower feet so they are as close together as
possible.
WARNING! High Voltage! Risk of electrical shock!
To reattach the PDU, reverse the process listed above.
Output/Bypass Breaker Operation
Output Status (Normal Operation)
Output coming from both UPS systems.
Output Status (Redundancy Mode)
Output coming from Primary UPS. Secondary UPS
needs repair. (Refer to Step 3, Part A.)
Output coming from Secondary UPS. Primary UPS
needs repair. (Refer to Step 3, Part B.)
Output Status (Power Mode)
Primary and Secondary UPS output coming from
Bypass. (Refer to Step 3, Part C.)
Note: Units will operate in Redundancy Mode up to 8 or 10kVA and switch to Power Mode at loads greater than 8 or 10kVA.
(for UPS maintenance or replacement)
Warning: Use extreme caution when handling the PDU.
Do not allow the contacts to touch any surface.
Parallel PDU Output Breakers
ON
Parallel PDU Output Breakers
ON
ON
Parallel PDU Output Breakers
ON
3C
5
11
Maintenance Bypass Breaker
OFF
Maintenance Bypass Breaker
OFF
OFF
Maintenance Bypass Breaker
ON