1-800-SAV-LEAD or 1-800-8-BATTERY (1-800-822-8837) or visit www.rbrc.com for recycling information. Tripp Lite offers a complete line of UPS System Replacement Battery Cartridges (R.B.C.).Visit Tripp Lite on the Web at www.tripplite.com/support/bat- tery/index.cfm to locate the specific replacement battery for your UPS.
2-Post (Telecom) Mounting To mount your equipment in a 2-post rack, you must purchase a Tripp Lite 2-Post Rackmount Installation Kit (model: 2POSTRMKITWM, sold separately) for each module installed. See the Installation Kit's owner's manual for complete mounting...
Mounting (Tower) Mount all modules in an upright, tower position using included base stands. The user must determine the fitness of hardware and procedures before mounting. The UPS system is shipped with two sets of plastic feet and extensions that can be used to tower mount the UPS’s power module, a battery module and a second battery module (9U total).
Features Before installing and operating your UPS, familiarize yourself with the location and function of the features of each component. Power Module Front Panel Controls 1. LCD DISPLAY: This backlit (16 × 2 character) dot matrix display indicates a wide range of UPS operating conditions and diagnostic data.
Features (Rear Panel) see page 7 for feature descriptions Power Module Detachable Power Distribution Unit Front Rear Left Side Battery Module...
Page 7
1. Input Terminal Block: Use these terminals to connect your power module to the detachable PDU. 2. External Battery Connector: Use this to connect one or more Tripp Lite battery modules to the power module. Remove the cover for access. The power module will not start without a connection to a charged battery module. Refer to the battery module owner’s manual for connection instructions and safety warnings.
Connection Hardwiring Cautions • Wiring must be done by a qualified electrician. • When making wiring connections, observe the cable connection regulations appropriate to your area [e.g. National Electrical Code (NEC) in the U.S.] at all times. Be sure to install an easily accessible disconnect switch in your installation wiring so you may cut off the UPS’s AC input during fires and other emergencies.
This will allow full network monitoring and control of your UPS system. Install on your computer the Tripp Lite PowerAlert Software appropriate to your computer's operating system. Note: RS-232 serial communications are unavailable for PowerAlert Software monitoring while the SNMP/WEB Card is installed in the UPS system's accessory slot.
Note: If desired, an optional hardwire detachable PDU is also available separately from Tripp Lite. Contact Tripp Lite for details. (Optional: During a hot-swap, the PDU can be housed in the back of the rack configuration using supplied PDU hanger brackets and hard- ware.
Page 11
Manual Bypass Operation (for power module maintenance or replacement) UPS Power/Battery Module Removal STEP 1. (Optional) Attach 2 PDU hanger brackets to the right-side, rear mounting rail using included screws and cage nuts. Important: determining where to attach your PDU hanger brackets will depend on your rack configuration. Generally it is recommended to mount the top bracket in the bottom two Mount Here square holes of the U space that the UPS and PDU are mounted in.
Page 12
Manual Bypass Operation (for power module maintenance or replacement) STEP 8: Loosen the screws in the contact cover . Slide the cover over the contacts . Tighten the screw to secure the cover. Warning: Use extreme caution when handling the PDU. Do not allow the contacts to touch any surface.
Failed Self-Test If a problem is detected during the self-test, the LCD will display a error message. If your UPS displays any of the following messages in its LCD, call Tripp Lite Technical Support at (773) 869-1234 for service. BAD BATTERY!
Operation continued normal Operation During normal operation, the first line of your LCD Display shows which operating mode your UPS is in: Online, Economy, On Battery, or Bypass. Online mode: The UPS provides AC power while utility power is available and switches to On Battery mode instantly (zero transfer time) if AC power is interrupted.
Operation continued Bypass Messages While in Bypass Mode, the UPS monitors its input voltage and passes that input power along to connected equipment. The UPS will not provide battery backup in Bypass Mode. If the output voltage deviates from an acceptable range (between 15% higher and 20% lower than nominal), the UPS displays the condition on its LCD and stops supplying output power to its load.
10 days of purchase. The warranties of all TRIPP LITE surge suppressors are null and void if they have been connected to the output of any UPS system. The warranties of all TRIPP LITE UPS Systems are null and void if a surge suppressor has been connected to its output receptacles.