Installation Space - LG multi V ARUB160BT3 Instruction Manual

Table of Contents

Advertisement

Installation Space

Individual Installation
n During the installation of the unit, consider service, inlet, and outlet and acquire the minimum space
as shown in the figures below.
Category
Front
4 sides are
walls
Only 2 sides
Front
are walls
Limitations on
the height of
the wall
(Refer to 4
side walls)
Installation Space
Front
Front
Front
Front
Front
Front
Front
No limit to the height of the wall
Front
• The height of the wall on the front side must be 1500mm or less.
• The height of the wall on the inlet(rear) side must be 500mm or less.
• There is no limit to the wall on the side.
• If the height of the walls on the front and the inlet side are higher than the
limit, there must be additional space on the front and the inlet side.
- Additional Space on the inlet side by 1/2 of h1.
- Additional Space on the front side by 1/2 of h2
- h2 = A(Actual height) - 1500
- h1 = B(Actual height) - 500
Case 1
(10mm≤Si d e Space≤49mm)
A≥10
B≥300
C≥10
D≥500
A≥10
B≥300
C≥10
D≥500
E≥20
A≥10
B≥300
C≥10
D≥500
E≥20
F≥600
A≥10
B≥300
C≥10
D≥300
E≥20
F≥500
A≥10
B≥300
A≥200
B≥300
No limit to the
E≥400
height of the wall
Installation Manual 17
Installation Space
Case 2
(Si d e Space≥49mm)
A≥50
B≥100
C≥50
D≥500
A≥50
B≥100
C≥50
D≥500
E≥100
A≥50
B≥100
C≥50
D≥500
E≥100
E≥500
A≥50
B≥100
C≥50
D≥100
E≥100
E≥500

Advertisement