Installation - LG multi V ARUB160BT3 Instruction Manual

Table of Contents

Advertisement

Installation

Installation
• Install at places where it can endure the weight and vibration/noise of the outdoor unit.
• The outdoor unit supports at the bottom should have width of at least 100mm under the unitʼs legs before being fixed.
• The outdoor unit supports should have minimum height of 200mm.
• Anchor bolts must be inserted at least 75mm.
The outdoor unit should
not be supported only by
the corner supports.
The location of the Anchor bolts
Chassis
UX2
UX3 (460V)
UX3 (220V)
20
Outdoor Unit
Capacity (HP)
8 ~ 12
14 ~ 20
14 ~ 18
Needed for outdoor units of 23kW or above
Center of the Unit
Needed for outdoor units of 23kW or above
Center of the Unit
Unit : mm
A(mm)
920
1240
1240
B(mm)
792
1102
1102