Hr Unit Pcb - LG multi V ARUB160BT3 Instruction Manual

Table of Contents

Advertisement

HR Unit PCB

#1 valve housing
#1 cooling valve LED(green)
#1 heating valve LED(red)
Switch for setup of HR Unit
1. Main function of SW02M
SW02M
1) Selection of the method for addressing valves of an HR unit (Auto/Manual)
Switch No.1 Off
2) Setting the zoning control
Normal
control
Zoning
control
SW02M
(Dip switch for setup of
the function of HR unit)
ON S/W
No.1
Method for addressing valves of an HR unit (Auto/Manual)
No.2
No.3
No.4
No.5
No.6
No.7
Use only in factory production (preset to "OFF")
No.8
Use only in factory production (preset to "OFF")
Auto
DIP S/W setting
#4 valve housing
SW01M/SW03M/SW04M
(Switch for manual valve
SW03M
SW04M
addressing)
Selection
Model of HR unit
Model of HR unit
Model of HR unit
Valve group setting
Valve group setting
Switch No.1 On
SW01M
Turn the dip switch of the zoning
branch on.
Ex) Branch 1,2 are zoning control.
SW01M
Installation Manual 79
HR Unit PCB
7-SEG
SW05M
(Switch for
addressing
HR unit)
SW01M
Zoning setting ("ON")
Manual

Advertisement

Table of Contents
loading