YASKAWA CDBR Series Installation Manual page 42

Ac drive option, braking unit, braking resistor unit
Hide thumbs Also See for CDBR Series:
Table of Contents

Advertisement

Fig. 22
Braking Unit Power Supply Voltage Selection
(Models CDBR-2045B, -2110B, -4090B, -5037B, -5110B, -5300B,
Indicating Cover Removed)
Table 3 Power Supply Voltage Selection Connector and Braking Start Voltage
200 V
Braking Start
Class*
Voltage
Power
(PN Bus-bar
Supply
Voltage)
Voltage
230 V
380 V (TYP)
220 V
365 V (TYP)
208 V
345 V (TYP)
200 V
330 V(TYP)
* Allowable voltage fluctuation is ±10%
200 V
575 V
400 V
Braking Start
Class*
Voltage
Power
(PN Bus-bar
Supply
Voltage)
Voltage
460 V
760 V (TYP)
440 V
730 V (TYP)
415 V
690 V (TYP)
400 V
660 V (TYP)
380 V
630 V(TYP)
43
4 OPERATION
class
class
400 V
200 V
208 V
220 V
230 V
class
500 V
575 V
575 V
Braking Start
Class*
Voltage
Power
(PN Bus-bar
Supply
Voltage)
Voltage
575 V
950 V (TYP)
500 V
825 V (TYP)
380 V
400 V
415 V
440 V
460 V