Capacity Compensation Rate For Pipe Length And Height Difference; Models: Aoyg18Kbta3 And Aoyg24Kbta3 - Fujitsu AUXG12KVLA Design & Technical Manual

3-unit multi-split type
Hide thumbs Also See for AUXG12KVLA:
Table of Contents

Advertisement

7. Capacity compensation rate for pipe length and height
difference
Indoor unit is higher than outdoor unit
Indoor unit
Connection pipe

7-1. Models: AOYG18KBTA3 and AOYG24KBTA3

NOTE: Values mentioned in the table are calculated based on the maximum capacity.
¢ Indoor unit: 7,000 Btu/h
Cooling
Indoor unit is higher than
outdoor unit *1
Indoor unit is lower than
outdoor unit *2
Heating
Indoor unit is higher than
outdoor unit *1
Indoor unit is lower than
outdoor unit *2
7-1. Models: AOYG18KBTA3 and AOYG24KBTA3
Height difference H
1
*
H
Outdoor unit
m
2.5
15
10
5
2.5
0.999
0
1.003
-2.5
1.003
-5
-10
-15
m
2.5
15
10
5
2.5
0.990
0
0.990
-2.5
0.988
-5
-10
-15
- 347 -
Indoor unit is lower than outdoor unit
Outdoor unit
H
Indoor unit
Connection pipe
Pipe length
5
10
15
0.956
0.977
0.963
0.992
0.985
0.971
0.996
0.989
0.975
1.000
0.993
0.979
1.000
0.993
0.979
1.000
0.993
0.979
0.993
0.979
0.979
Pipe length
5
10
15
0.977
0.993
0.977
1.000
0.993
0.977
1.000
0.993
0.977
1.000
0.993
0.977
0.997
0.991
0.975
0.995
0.988
0.972
0.983
0.967
0.962

7. Capacity compensation rate for pipe length and height difference

2
*
20
25
0.942
0.928
0.950
0.936
0.957
0.943
0.961
0.947
0.965
0.951
0.965
0.951
0.965
0.951
0.965
0.951
0.965
0.951
20
25
0.958
0.939
0.958
0.939
0.958
0.939
0.958
0.939
0.958
0.939
0.956
0.937
0.953
0.934
0.948
0.930
0.944
0.925