11-4.Ceiling Type - Fujitsu AUXG12KVLA Design & Technical Manual

3-unit multi-split type
Hide thumbs Also See for AUXG12KVLA:
Table of Contents

Advertisement

11-4. Ceiling type
PCB
External input
Operation/Stop
Forced stop
Indoor unit
Operation/Stop
Forced
thermostat off
External input
and output
(UTY-XCSX)
¢ External input
With using external input function, some functions on this product can be controlled from an external
device.
• "Operation/Stop" mode can be selected with function setting of indoor unit.
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 150 m.
• The wire connection should be separate from the power cable line.
 Indoor unit
Indoor unit functions such as Operation/Stop can be done by using indoor unit terminals.
*1: The switch can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
11-4. Ceiling type
CN65
CN47
(Ext.in/out PCB)
(Ext.out)
Terminal
(Ext.in)
Fig. Indoor unit PCB
External output Connector
Operation status
Error status
Indoor unit fan
operation status
External heater
output
Operation status
Error status
Indoor unit status
External heater
output
Rotary switch
SW2
SW1
Fig. External input and output PCB
Input select
Terminal
Dry contact
CN47
Input 1/
Input 2
Dry contact/
Apply voltage
Input 1
Output 1
Output 2
Output 3
- 152 -
External
Input
connect kit
signal
(Optional
parts)
Edge
UTY-XWZXZG
Edge/
Pulse
Edge
Terminal
1
2
11. External input and output