10. Safety devices

Indoor unit
Model name
type
AUXG07KVLA
AUXG09KVLA
Compact
AUXG12KVLA
cassette
AUXG14KVLA
AUXG18KVLA
ARXG07KSLAP
ARXG09KSLAP
Mini duct
ARXG12KSLAP
ARXG14KSLAP
ARXG18KSLAP
ARXG07KLLAP
ARXG09KLLAP
ARXG12KLLAP
ARXG14KLLAP
Slim duct
ARXG18KLLAP
ASYG07KGTB
ASYG09KGTB
ASYG12KGTB
ASYG14KGTB
ASYG18KMTB
ASYG07KMTB
ASYG09KMTB
ASYG12KMTB
Wall mounted
ASYG14KMTB
ASYG07KMCC
ASYG09KMCC
ASYG12KMCC
ASYG14KMCC
ASYG07KETA
ASYG07KETA-B
ASYG09KETA
ASYG09KETA-B
ASYG12KETA
ASYG12KETA-B
ASYG14KETA
ASYG14KETA-B
PCB* fuse
Fan motor thermal protector
Activate: 100 ±15°C
Fan motor stop
Reset: 95 ±10°C
Fan motor restart
Activate: 135 ±15°C
Fan motor stop
250 V, 5 A
Reset: 105 ±15°C
Fan motor restart
Activate: 135 ±15°C
Fan motor stop
Reset: 115 ±15°C
Fan motor restart
Activate: 110 ±15°C
Fan motor speed down
Reset: 110 ±15°C
Fan motor speed recover
Activate: 125 ±10°C
Fan motor stop
Reset: 100 ±10°C
Fan motor restart
Activate: 125 ±24°C
Fan motor stop
Reset: 100 ±25°C
Fan motor restart
Activate: More than 95 °C
Fan motor speed down
Reset: 95 °C or less
Fan motor speed recover
Activate: 125 ±10 °C
250 V, 3.15 A
Fan motor stop
Reset: 100 ±10 °C
Fan motor restart
Activate: 170
Fan motor stop
Reset: 145
Fan motor restart
Activate: 110 ±15°C
Fan motor speed down
Reset: 110 ±15°C
Fan motor speed recover
Activate: 125 ±10°C
Fan motor stop
Reset: 110 ±10°C
Fan motor restart
- 129 -
Terminal
thermal
fuse
102°C Off
+25
°C
-30
+25
°C
-30
102°C Off
Float
switch
10. Safety devices