Rinnai RLX94i Installation And Operation Manual page 17

Direct vent tankless water heater for indoor/outdoor applications only
Table of Contents

Advertisement

Available languages

Available languages

Isolation Valves and Pressure Relief Valve
The isolation valves provide the ability to isolate the
water heater from the structure's plumbing and allow
quick access to flush the heat exchanger. Check with
local codes to determine if a pressure and
temperature relief valve is required. The included
valves meet American National Standard (ANSI
Z21.10.3) / Canadian Standard (CSA 4.3) and are
ANSI/NSF 61 approved for potable water.
Isolation Valves Installation Instructions:
NOTICE
When unscrewing the UNION FITTING, Be careful not
to lose any washers and/or gaskets that may be
present.
1.
Wrap the ends of the threaded water inlet and
outlet on the tankless water heater, as well as
the threaded end of the approved pressure relief
valve with a minimum of 5 wraps of Teflon®
tape.
2.
Install the pressure relief valve to the 3/4"
threaded port on the HOT (RED) water service
valve (will be adjacent to or above the cut off,
never below). See Pressure Relief Valve Section
for proper installation requirements.
3.
Loosen the 3/4" union nut on the HOT water
valve and connect to the HOT water outlet on
the tankless water heater. If nut is removed,
ensure that you realign the tailpiece accurately
to the valve, and that the black washer and/or
gasket is properly positioned.
4.
Align the direction of the HOT water drain to the
desired position.
5.
Tighten the union assembly to the HOT water
valve. DO NOT over torque.
6.
Repeat steps 3-5 for the COLD water valve.
(BLUE valve) for connection to the COLD water
inlet on the tankless water heater.
7.
Connect the INLET on the COLD water valve to
the MAIN SOURCE of the water supply.
8.
Connect the OUTLET on the HOT water valve to
the HOT WATER plumbing system.
9.
Ensure that both drain valves are in the
closed/"OFF" position.
A
B
C
E
A Pressure Relief Valve (PRV)
B
C
D Cold Drain Valve
E
F
Pressure Relief Valve (PRV) Installation Instructions:
The PRV must be connected to the 3/4" threaded port
on the HOT (RED) water service valve (will be adjacent
to or above the shut off, never below). Installation
must maintain a ¾" port size with no shut off valve or
line restriction in-between the appliance and the PRV.
The discharge line from the PRV should pitch
downward and terminate 6" above drains where
discharge will be clearly visible. The discharge end of
the line shall be plain (unthreaded) and a minimum of
¾" in diameter. The discharge line material must be
suitable for water at least 180° Fahrenheit. No valve
of any type may be installed in the discharge line of
the pressure relief valve.
Pressure Relief Valve Maintenance:
For proper care of this approved pressure relief valve,
it is recommended that the valve is manually
operated once a year. In doing so, it will be necessary
to take precautions with regard to the discharge of
potentially scalding hot water under pressure. Ensure
discharge water has a safe place to flow. Contact
with your body or other property may cause damage
or harm.
Please note that only the PRV in this package is
certified by CSA International as an approved item.
VC Series Manual
D
F
PRV Discharge Outlet
Hot Drain Valve
Hot Ball Valve
Cold Ball Valve
17