malfunction  or  power  distribution  malfunction. 
Please  press  down  the  emergency  stop  on  the 
control panel, so that to immediately shut down the 
generator set. Under normal condition, please do not 
use emergency stop to stop the generator set. 
3.2.6 
Normal stop the generator set 
Before  stop  the  generator  set  under  normal 
condition, first separate the load from this generator 
set,  then  run  the  generator  set  with  no  load  for  a 
certain  period  of  time(3  to  5  minutes),  so  that  to 
make  sure  the  generator  set  become  fully  cooled, 
after  that  the  generator  set  can  be  stopped.  (Please 
do not make cooling running under idle speed) 
For  some  generator  sets  which  have  been  installed 
with  stop  solenoid,  it  is  impossible  to  stop  the 
generator  set  by  cutting  off  the  key  switch  on  the 
control panel. Correct operation is: to press the stop 
button  when  the  power  of  the  control  panel  being 
resumed, only in this way you can stop the generator 
set.(press  the  stop  button  until  the  generator  set 
fully stop running) 
3.3 
After Running 
After  the  generator  set  stop  running,  it  is  necessary 
to carry on following jobs: 
◆To  check  if  the  generator  set  has  "three  leakage" 
(lubricant, fuel, anti‐freeze leakage) 
◆Shut down fuel valve 
◆Shut  down  air  inlet  and  air  exhaust  facility  in  the 
generator set's working room(when necessary) 
◆Shut down the generator set's output air switch 
◆Shut down the power key switch on the control panel, 
take out the key and keep it in good condition (when 
necessary) 
When the generator set need to be shut down for a 
long time or is under maintenance, please dis‐connect 
the  start  battery's  negative  polar  cable,  and  fully 
discharge  the  fuel  and  anti‐freeze  liquid  when 
necessary. 
For  the  self‐start  generator  set,  some  of  the  above 
terms  are  not  applicable.  After  the  self‐start 
generator set stops, please keep it in the same status 
as that of pre‐start (ready to start), so that it can start 
at any time under emergency cases. 
3.4
 Record for running 
For  each  running  operation,  user  shall  make  record. 
Running record has various forms. The basic content 
shall  cover:  the  time  period  for  this  running, 
accumulated  running  time  for  this  generator  set, 
value  of  engine's  oil  pressure  gauge,  temperature 
meter,  output  voltage,  frequency,  maximum 
power(current) etc. and the running situation, and if 
there is any malfunction warning / generator set shut 
down etc. 
Only  when  the  correct  and  complete  record  for 
running  (maintenance)  has  been  kept  very  well,  the 
user  can  get  correct  and  excellent  after  sales 
(warranty) service. 
3.5 
Matters need attention 
Warning: 
!  When  engine's  temperature  is  very  low,  the  time 
period  for  idle  speed  shall  be  properly  extended. 
However, when the generator set become warm, it is 
not allowed to run the generator set with idle speed 
for a long time, it is not allowed to continuously run 
the  generator  set  under  empty  or  small  load.  Such 
kind of operation will cause server carbon deposition 
and  oil  leakage  in  engine's  turbo‐charger  and 
exhaust system. 
!  It  is  not  allowed  to  run  the  generator  set  with 
overload in long time period, otherwise malfunction 
will occur, which will decrease the generator set's life 
expectancy.       
!  It  is  forbidden  to  detach  or  change  the  components 
of the generator set when it is running.       
!  The  coolant  which  is  going  to  be  added  need  to  be 
the same specification as that of the original cooling 
system. When open the cover of water adding hole, 
please  pay  attention  to  the  temperature  and  avoid 
the steam or high temperature coolant burst forth to 
hurt people.   
!  When  discharge  the  high  temperature  lubricant  oil, 
please avoid being burnt.   
!  The  fuel  being  used  shall  be  conform  to  national 
standard,  otherwise  it  will  cause  malfunction  of  the 
engine's fuel pump or fuel injector.   
!  For  the  engines  installed  with  turbo‐charger,  it  is 
suggested  not  to  add  50%  or  above  instant  load  to 
the generator set. Otherwise this will cause relatively 
big stall to the generator set. 
! For the large electricity consumption equipment, it is 
suggested  that  the  users  need  to  use  methods  such 
as  voltage  decrease  and  frequency  change  etc.  to 
control the start, so that to reduce big impact on the 
generator set when the facility start. 
!  Backup  generator  sets  or  the  generator  sets  which 
haven't been run for a long time, it is suggested that 
these kinds of generator sets shall be run to working 
temperature at least one time a month. These kinds 
of  generator  sets  need  to  be  continuously  run  with 
full load for 4 hours at least one time per year. 
!  For  the  generator  sets  which  are  connected  in 
parallel  and  controlled  by  manual,  operators  must 
make  sure  they  are  running  synchronously(same 
frequency,  same  phase‐sequence,  same  phase,  and 
same voltage) before switch on, and must switch off 
before  trying  to  stop  the  generator  sets  group. 
13