5.3 Maintenance

The following inspections and maintenance tasks are recommended at least two times per
year for best controller performance.
 Check that the controller is securely mounted in a clean and dry environment.
 Check that the air flow and ventilation around the controller is not blocked. Clear all
dirt or fragments on the heat sink.
 Check all the naked wires to make sure insulation is not damaged for serious
solarization, frictional wear, dryness, insects or rats etc. Maintain or replace the wires if
necessary.
 Tighten all the terminals. Inspect for loose, broken, or burnt wire connections.
 Check and confirm that LED or LCD is consistent with required. Pay attention to any
troubleshooting or error indication .Take necessary corrective action.
 Confirm that all the system components are ground connected tightly and correctly.
 Confirm that all the terminals have no corrosion, insulation damaged, high temperature
or burnt/discolored sign, tighten terminal screws to the suggested torque.
 Inspect for dirt, insects and corrosion, and clear up.
 Check and confirm that lightning arrester is in good condition. Replace a new one in
time to avoid damaging of the controller and even other equipments.
Cooling
fins
When the temperature of cooling fins of
of
controller
over
controller reach 85 ℃, the controller will
temperature
cut input and output circuit; when it is
lower than 75 ℃,the controller will
automatically recover the connection of
input and output circuit.