WESTECH VS Series Instruction Manual page 39

Solar charge controller
Table of Contents

Advertisement

Charging and discharging
circuit is off and the BATT
of
monitoring
interface
shows OVD.
Charging and discharging
circuit is off and the BATT
of
monitoring
interface
shows Over Temp.
Charging and discharging
circuit is off and the BATT
of
monitoring
interface
shows Error.
Discharging circuit is off
and
the
LOAD
monitoring interface shows
OverLoad.
Battery
over
voltage
Operating
ambient
temperature
(local
temperature
sensor)
or
battery
temperature
(remote
temperature
sensor)
over
temperature
Battery
voltage
inspection
fault
Load
power
of
surpasses
nominal
power
Measure and judge if the voltage of
battery is too high, and switch off the
wiring of solar array.
When operating ambient temperature or
battery temperature reaches more than
85°C, controller will automatically cut off
input and output circuit.
When the temperature is less than 75°C,
controller will automatically recover the
connection of input and output circuit.
Please restart controller, if the fault still
exists, immediately cut off charging and
discharging circuit and contact the
supplier to make maintenance.
Please reduce the number of electric
equipments. When load power reaches
1.05-1.25 times, 1.25-1.5 times and 1.5
times more than nominal value, controller
will automatically close loads in 60
seconds, 5 seconds and 1 second,
respectively. It is reactivated after delayed
5 seconds for the first time, 10 seconds for
the second time, 15 seconds for the third
time, 20 seconds for the fourth time and
25 seconds for the fifth time. If over 5
36