Preparations Before Installation - Daikin VRV FXMQ50P7VEB9 Installation And Operation Manual

Table of Contents

Advertisement

P
REPARATIONS BEFORE INSTALLATION
1
Relation of ceiling opening to unit and suspension bolt position.
(See figure 5)
Model
20~32
40
50~80
100+125
1
Indoor unit
2
Pipe
3
Suspension bolt pitch (x4)
4
Suspension bolt pitch distance
For installation, choose one of the possibilities as listed further.
Standard rear suction
(See figure 6a)
1
Ceiling surface
2
Ceiling opening
3
Service access panel (optional accessory)
4
Air filter
5
Air inlet duct
6
Duct service opening
7
Interchangeable plate
Installation with rear duct and duct service opening
figure 6b)
Installation with rear duct, no duct service opening
figure 6c)
NOTE
Before installation of the unit (in case of installation
with duct, but no duct service opening): modify the
position of the air filters.
1
Remove the air filter(s) at the
outside of the unit
2
Remove the interchangeable
plate
3
Install the air filter(s) from the
inside of the unit
4
Reinstall the interchangeable
plate
NOTE
When installing an air inlet duct, select fixing screws
that shall stick out maximum 5 mm at the inside of the
flange to protect the air filter from damage during
maintenance of the filter.
1
Air inlet duct
2
Inside of the flange
3
Fixing screw
Installation and operation manual
3
A (mm)
B (mm)
550
586
700
738
1000
1038
1400
1438
(See
(See
3
1
2
4
1
2
≤5 mm
3
Mounting the air inlet panel with a canvas connection
figure 7a)
Mounting the air inlet panel directly
1
Ceiling surface
2
Ceiling opening
3
Air inlet panel (Optional accessory)
4
Indoor unit (Back side)
5
Canvas connection for air inlet panel (Optional accessory)
Model
20~32
40
50~80
100+125
Bottom suction
(See figure 7c)
NOTE
The unit can be used with bottom suction by replacing
the interchangeable plate by the air filter holding plate.
1
Air filter holding plate with air filter(s)
2
Interchangeable plate
For other installation than standard installation, contact
NOTE
your Daikin dealer for details.
2
The fan speed for this indoor unit is preset to provide standard
external static pressure.
3
Install the suspension bolts.
(Use M10 size bolt for the suspension bolt.) Use anchors for
existing ceilings, and a sunken insert, sunken anchors or other
field supplied parts for new ceilings to reinforce the ceiling in
order to bear the weight of the unit.
Installation example
(See figure 3)
1
Anchor
2
Ceiling slab
3
Long nut or turn-buckle
4
Suspension bolt
5
Indoor unit
NOTE
All the above parts are field supplied.
(See
(See figure 7b)
A (mm)
610
760
1060
1460
FXMQ50-125P7VEB9
VRV System air conditioners
3P468515-4 – 12.2016