Sr100Hi- Dc Settings - Helios HPS-PS-STANDALONE-SR100HL User Manual

100w dc ups
Table of Contents

Advertisement

SR100Hi Series - 100W DC UPS
8. SR100Hi– DC SETTINGS
Parameter
V nominal
V output (20°C)
BatDetect (mins)
Vpres:
Vbatl:
Vshutd:
Vdisco:
Bccl (%)
Comms
BCTim (mins)
CC Mins:
CC Hrs:
CC Days:
MfiBCT:
BatDetect:
Time between battery detections
Vpres:
Voltage threshold for battery detection and BCT. Note that if the voltage drops to this level dur-
Vshutd:
Internal voltage level of the power supply during battery detection and battery condition tests.
Vbatl:
BAT LOW alarm voltage level
Vdisco:
Voltage at which the load is disconnected from the battery during mains fail
Bccl:
Battery charge current limit as percentage of the rated power supply current
Comms
Communication mode of PSU: F = continuous data stream of status
BCTim:
Length of battery condition test
CC Mins:
Time in minutes between automatically scheduled BCTs
CC Hrs:
Time in hours between automatically scheduled BCTs
CC Days:
Time in days between automatically scheduled BCTs
Note: The total time interval between battery condition tests (BCTs) is the sum total of the three 'CC' settings
MFiBCT:
Time in minutes before the mains fail check during the BCT (only applicable to SR100)
Scheduled BCT
disabled
New Zealand: sales@heliosps.co.nz - Australia: sales@heliosps.com.au - Middle East & Asia: sales@heliosps.asia
Default Settings
12
24
30
13.8
27.6
34.5
60
60
60
12.2
24.4
30.5
11
22
27.5
11.5
23
28.7
10
20
25
100
100
100
M
M
M
20
20
20
40
40
40
23
23
23
27
27
27
30
30
30
Actual settings if different from default
36
48
41.4
55.2
60
60
36.6
48.8
33
44
34.5
46
30
40
100
100
M
M
20
20
40
40
23
23
27
27
30
30
88888 88
www.heliosps.com
8

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sr100hi series

Table of Contents