SR100Hi Series - 100 W DC UPS

2. INTRODUCTION:

The No-Break ™DC SR100Hi switch mode power supply is designed to provide DC power to lead acid batteries for critical
back up applications.
No-Break ™ DC UPS systems maximise the integrity of standby battery installations, whilst optimising the life
and availability of back up batteries.

3. SR100Hi Series - SYSTEM BLOCK DIAGRAM

AC MAINS
LED
POWER
OFF
OK LED
BATTERY
LED
SYSTEM
ON
OK LED
MAINS FAIL /
ALARM
POWER SUPPLY
OFF
FAIL ALARM
BATTERY
ALARM
SYSTEM
OFF
FAIL ALARM
4. OPERATION OF ELECTRONIC CIRCUIT BREAKER (ECB) FOR PROTECTION OF BATTERY CIRCUIT & BATTERY
The ECB will operate on overcurrent as above & is also activated for the low voltage disconnect function on mains fail (no input pow-
er). It will reset when input power is restored, or can be manually reset by briefly shorting the BAT- and LOAD- terminals together
when there is no input power.
New Zealand: sales@heliosps.co.nz - Australia: sales@heliosps.com.au - Middle East & Asia: sales@heliosps.asia
POWER CONVERSION
OUTPUT VOLTAGE, CURRENT
LIMIT & BATTERY CHARGE
CURRENT CONTROL
BATTERY
BATTERY
MANAGEMENT
CURRENT
& ALARM
SENSE
CIRCUIT
Max. allowable
load amps
(x I rated)
Short circuit condition,
ECB trips within 2ms
6x I
for 300ms max.
rated
6
1.5
2ms
300ms
ELECTRONIC
REVERSE
BREAKER
POLARITY
CIRCUIT
FUSE
NORMAL OPERATION
LOAD CURRENT < PSU MAX CURRENT
No Mains
1.5 x I
until LV disconnect
rated
operates
Time
I
= 0
PSU
55555 55
I
LOAD
LOAD +
LOAD -
I
CHARGE
BATTERY +
BATTERY TEMP.
SENSOR
BATTERY -
www.heliosps.com
5