Addressable waterproof self testing non-maintained emergency ceiling mounted luminaires

Advertisement

Automatic Operational Test
This test includes all the operations that are
provided in manual test and is conducted
automatically every 15 days. In order to be
performed, the mains power supply and the
battery should be connected.
Automatic Autonomy Test
The Automatic Autonomy Test tests the
device's back up operation and emergency
duration. This test is conducted automatically
every 6 months. In order to be performed, the
mains power supply should be connected and
the battery must be fully charged. If the
battery is not fully charged, the test is
postponed until the battery is completely
charged. If during this test, the autonomy is
less than nominal then the battery fault LED
will permanently be on and the battery must
be replaced.
Back Up Operation
The autonomy duration of battery during
emergency mode must be at least as the one
stated
in
the
characteristics. During emergency mode, a
light source test is also performed.
Resetting Errors
Hold the A-1900 card in TEST position for 10
to 15 seconds in order to delete all LED
indicated errors. Then
regular operation mode.
ADDRESSABLE COMMUNICATION
The luminaire has the ability to be connected
to GR-6500 panel. In order to do so, the
luminaire's address has to be unique in the
same bus. For more details see page 3
(installation instruction).
Page 2 from 9
list
of
the
technical
the device enters
ΑΤΤΕΝΤΙΟΝ!!!
1. Operations for installation, maintainance
or testing must be done by authorized
personnel only.
2. The device must be connected to the
mains power supply through a fuse that is
dependent on the total line's power load.
3. In case of battery or lamp replacement,
these must be replaced by parts with same
type, by the manufacturer or by a competent
person.
4. In case of inactive use for a period
greater than 2 months, disconnect the
battery by pulling out the battery's connector.
5. I s not allowed to discard batteries in
t i
to common trash bins, they must be
discarded only
points. Do not incinerate.
Indication LED status (mains on)
Charge
On: Fully charged.
Οff: No battery (No charging current
or disconnected battery).
Blink: Charging.
Lamp Fault
Οn: Faulty LED.
Off: LED OK.
Blink: Operational Test.
Battery Fault
Οff: Battery OK.
ON (With Charge LED ON): Autonomy or
low battery problem (the battery must be
replaced).
Blink (With Charge LED Off): Autonomy test
is performed.
Indicators
Charge
in battery recycling
Battery
Fault
Lamp
Fault
923493002_09_001