16 Configuration
1 Operate the unit in fan only mode prior to using the airflow
automatic adjustment function.
2 Stop the air conditioning unit.
3 Set the value number "—" to 03 for M 11(21) and SW 7.
4 Start the air conditioning unit.
Result: The operation lamp lights up and the unit starts the fan
operation for airflow automatic adjustment.
5 After airflow automatic adjustment is finished (air conditioning
unit will stop) check if the value number "—" is set to 02. If there
is no change, perform the setting again.
Setting content:
Airflow adjustment is OFF
Completion of automatic airflow adjustment
Start of automatic airflow adjustment
To set external static pressure by the user interface
Check the indoor unit setting: the value number "—" must be set to
01 for M 11(21) and SW 7.
1 Change the value number "—" according to the external static
pressure of the duct to be connected as in table below.
M
SW
External static pressure (Pa)
13(23)
6
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
Setting: Air volume when thermostat control is OFF
This setting must correspond with the needs of the user. It
determines the fan speed of the indoor unit during thermostat OFF
condition.
1 If you have set the fan to operate, set the air volume speed:
(1)
Field settings are defined as follows:
• M: Mode number – First number: for group of units – Number between brackets: for individual unit
• SW: Setting number
• —: Value number
: Default
(2)
Fan speed:
• LL: Low fan speed (set during thermostat OFF)
• L: Low fan speed (set by the user interface)
• Setup volume: The fan speed corresponds to the speed the user has set (low, medium, high) using the fan speed button on the user
interface.
• Monitoring 1, 2: The fan is OFF, but runs for a short time every 6 minutes to detect the room temperature by LL (Monitoring 1) or by L
(Monitoring 2).
Installation and operation manual
22
During thermostat
OFF at cooling
operation
During thermostat
OFF at heating
operation
(1)
Then
M
SW
11(21)
7
01
02
03
Setting: Time to clean air filter
This setting must correspond with the air contamination in the room.
It determines the interval at which "Time to clean filter" notification
is displayed on the user interface.
(1)
±2500 h (light)
±1250 h (heavy)
50
Notification ON
60
Notification OFF
70
Setting: Thermostat sensor selection
80
This setting must correspond with how/if the remote controller
90
thermostat sensor is used.
100
When the remote controller thermostat
110
120
Used in combination with indoor unit
130
thermistor
140
Not used (indoor unit thermistor only)
150
Used exclusively
160
Setting: Thermostat differential changeover (if remote sensor is
180
used)
200
If the system contains a remote sensor, set the increase/decrease
increments.
If you want to change increments to...
1°C
0.5°C
Setting: Differential for automatic changeover
Set temperature difference between cooling setpoint and heating
setpoint in automatic mode (availability depends on the system
type). Differential is cooling setpoint minus heating setpoint.
If you want...
(2)
LL
(2)
Setup volume
(a)
OFF
(2)
Monitoring 1
(2)
Monitoring 2
(2)
LL
(2)
Setup volume
(a)
OFF
(2)
Monitoring 1
(2)
Monitoring 2
(a)
Only use in combination with optional remote sensor or when
setting M 10 (20), SW 2, — 03 is used.
If you want an interval of...
(air contamination)
sensor is...
(1)
Then
M
SW
12 (22)
6
01
02
03
04
05
12 (22)
3
01
02
03
04
05
(1)
Then
M
SW
10 (20)
0
01
02
3
01
02
(1)
Then
M
SW
10 (20)
2
01
02
03
(1)
Then
M
SW
12 (22)
2
01
02
FXMA-A
VRV system air conditioner
3P680922-1A – 2022.01