(H) Change the shift temperature in heating mode
If the indoor unit is installed at high location (ex. ceiling level), the thermostat tends to turn off at heating mode
because of the hot air temperature around ceiling level. In order to solve the problem, the shift temp. (valid while
heating only) is set when shipped from factory.
If the shift temp. is not enough (ex. the indoor unit is installed at position higher than 3 m), the shift temp. can
be set with remote controller from +1 to +10 deg. manually as follows:
a) Press the TEST / CHK button for more than 4 seconds.
AIR FLOW
UNIT
R.C.
FLAP
SET
CL
b) In case of group control, if you want to change all units in group control collectively, proceed next step
remaining ALL displayed.
If you want to change a unit individually, select the indoor unit address (UNIT No.) with UNIT button.
c) Select the CODE No. 06 with
d) Choose the shift temp with
AIR FLOW
UNIT
UNIT No.
R.C.
FLAP
TIMER SET
SET
CL
e) Press the SET button.
CODE No. 06, SET DATA and
f) If you made a mistake, press the CL button.
g) Finally, press the TEST / CHK button.
MODE
No.
0365_M_ I
#
$
,
#
$
,
MODE
No.
SET TEMP.
CODE
No.
SET TEMP.
FAN SPEED
SETTING
SET
DATA
ON
OFF
TEST / CHK
0366_M_I
change from flashing to ON state.
(SET TEMP) button.
¿
(
) button.
EX:
UNIT No. 1–6
CODE No. 06
Shift temp. +5 deg