Function; Room Temperature Control - Technibel KPAVM93R5TAA Technical Data & Service Manual

Table of Contents

Advertisement

4. FUNCTIONS

4-1 Room temperature control

The unit adjusts room temperature by turning the outdoor unit's compressor ON and OFF. This process is
controlled by the thermostat located in the indoor unit. The figures on this and the next page show how each
part of the system performs as the room temperature changes and the thermostat activates the compressor to
start (thermo ON) or stop (thermo OFF). Fig. 1 shows about the cooling cycle, and Fig. 2 shows about the
heating cycle.
(A) Cooling
BODY SENSOR
T+1°C
SET TEMP . T °C
T-1°C
COMPRESSOR
1
OUTDOOR FAN
(H, M or L)
INDOOR F AN
DRAIN PUMP
DEW PROOF
HEATER
Once the compressor Starts, it keeps running for 5 minutes.
Once the compressor stops , it will not start running again for 3 minutes.
If you change the operation mode ( HEAT, DRY, COOL, or FAN ) during the cooling cycle,
the control circuit stops the compressor for 3 minutes.
the compressor is not controlled by the room sensor.
Thermo ON: When room temperature rises 1°C (2°C when set on body sensor) above
Thermo OFF : When the room temperature is -1°C below the set temperature T°:
THERMO. OFF
MORE THAN
3 MINUTES
5 MINUTES
ON
OFF
ON
OFF
ON
OFF
ON
OFF
1. Refer to 2-4 Outdoor Fan Speed Control
Chart Summary and Explanations
the set temperature T°, (T°+1 °C or T°+2°C when set on body sensor):
(THERMO. ON)
5 MINUTES
ON
ON
SET SPEED
ON
ON
Compressor
ON
Compressor
OFF
13
(THERMO. OFF)
ROOM TEMP .
THERMO. ON
MORE THAN
MORE THAN
3 MINUTES
5 MINUTES
OFF
ON
OFF
ON
OFF
ON
OFF
ON
1573_X_S