(C) Check the sensor temperature readings
The air conditioner has thermo sensors which are used to control the unit.
Each sensor has an address which is made up of the indoor unit address, and the sensor address. The indoor
unit address is used only when several units are hooked up to one remote controller (group control). If there is
only one unit, made up of one indoor and one outdoor unit, then only the sensor address should be put in, as
shown in the procedure below.
Follow this procedure to display the temperature of each sensor:
a) On the remote controller, press both TEST / CHK and CL buttons at the same time for more than 4
seconds.
b) The UNIT No., the address and temperature of the sensors instead of its usual information will flash on the
display.
Following example shows the UNIT No. (Indoor unit address) is fixed at 01– 01.
In case of group control, select the UNIT NO. (Indoor unit address) which you want to check with UNIT button.
Each time you press the , (SET TEMP.) button you can select a different sensor, and the display shows the
sensor address and temperature as shown below.
NOTE
Do not press TIMER SET button during the procedure.
AIR FLOW
UNIT
MODE
R.C.
No.
FLAP
°C
SET
CL
AIR FLOW
UNIT
R.C.
No.
FLAP
MONIT OR
SET
CL
45
UNIT No. (Indoor unit address)
MODE
Sensor address
Sensor temperature °C