T+2°C (T+1°C)
SET TEMP .
T °C
T-2°C (T-1°C)
5 MINUTES
COMPRESSOR
OUTDOOR FAN
INDOOR FAN
Body sensor
The indoor fan speed is automatically set to L and cannot be adjusted to M or H.
When the set temperature is either 18 or 19°C, the set temperature is considered the same
as 20°C.
operation mode.

4-11 Auto-flap Control (Indoor Unit: 4-Way Air Discharge)

Auto flap can control the air flow in 5 steps.
Operation mode
Cooling/dehumidifying
Fan
Heating
Standby for heating
(1) When the unit is stopped, the Auto-flap returns to F5 position.
(2) When the airflow direction is set (an optional setting), the auto and Swing settings will be released. To
return the mode to auto-flap control, change the operation mode.
(3) Once Auto-flap is set, the flap position will be input in the memory.
(4) When the operation mode is changed, the unit starts to search flap position. (if a search action for
sensing flap position is not succeeded in one minute, only the swing is operated.)
ROOM TEMP
3 MINUTES
ON
OFF
ON
OFF
F1
F2
F3
F4
Cooling F1~F3
Heating F1~F5
Automatic setting
F2
F2
F4
F2 (The flap returns to the original position after release
of standby mode)
ON
ON
L
60°
F5
1328_M_I
Flap position
Optional setting
F1 - F2 - F3 - Swing
F1 - F2 - F3 - F4 - F5 Swing
F1 - F2 - F3 - F4 - F5 Swing
22
AREA
OFF
ON
OFF
ON
0449_M_S
Fig. 20