Technibel GR9FI65R5I Series Installation Instructions Manual page 5

Hide thumbs Also See for GR9FI65R5I Series:

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
DELAYED FUSE
220 - 240 V ~ 50 Hz
380 - 415 3N ~ 50 Hz
MODEL
GR9FI65R5
mm
MONO SPLIT
DUAL SPLIT
GR9FI65R7
TRIAL SPLIT
Supply power wire A:
Multipolar electric wire. Size and length of the suggested electric wire are showed on table "electrical data". The wire
must be Mod. H07RN-F (according to CEI 20-19 CENELEC HD 22). Make sure the length of the conductors between
the fixing point and the terminals allows the straining of the conductors L, N before that of the grounding.
Connecting wire B (SHIELDED):
Bipolar electric shielded wire; size and length of the suggested electric wire are showed on table "electrical data".
The wires have not to be lighter than Mod. H05VVC4V5-K (according to CEI 20-20 CENELEC HD21).
Connecting wire C (with ground conductor):
Multipolar electric wire; size and length of the suggested electric wire are showed on table "electrical data". The
wires have not to be lighter than Mod. H07RN-F (according to CEI 20-19 CENELEC HD22).
ADDITIONAL MATERIAL REQUIRED FOR INSTALLATION (NOT SUPPLIED)
Deoxidized annealed copper tube for refrigerant tubing connecting the units of the system; it has to be insulated with
foamed polyethylene (min. thickness 8mm).
MODEL (INDOOR UNIT)
OUTER DIAMETER
A
B - C
PVC pipe for condensate drain pipe (ø int.18mm) in length suitable to let the condensate flow into the outside drainage.
Anti-freeze oil for flare connections (about 30g.).
Electric wire: use insulated copper wires of size and length as shown at paragraph "SYSTEM WIRING DIAGRAMS".
POWER SUPPLY
AC 380-415V
3PHASE 50Hz
Main switch for disconnection from the supply line must have a contact separation
in all poles that provides full disconnection under category III overvoltage conditions.
LENGTH, SIZE WIRES AND DELAYED FUSE
L ("A") m
2
2,5
20
NARROW TUBE
MIN. THICKNESS
6,35 mm
6,35 mm
L ("B") m
0,75
35
30
25
OUTER DIAMETER
0,8 mm
9,52 mm
0,8 mm
12,7 mm
5
3 INDOOR UNITS
3 PHASE
L ("C") m
1,5
16 A
35
30
25
12,5 A
LARGE TUBE
MIN. THICKNESS
0,8 mm
0,8 mm
EG

Advertisement

loading